UPS2000-G-3 kVA
User Manual (CTC)
A Alarm Handling
Issue 02 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
67
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
temperature.
Keep the air intake and
exhaust vents of the
UPS unobstructed.
Clean off the foreign
objects around the fan.
If the alarm persists,
contact Huawei
technical support for
repair.
0032-01
Batt.
OVP
Critical
Automatic
clear
An alarm is generated, and
the battery lifespan is
affected.
Possible causes:
The configured number
of batteries is less than
the actual number.
The actual number of
batteries does not meet
specifications.
The charger is
abnormal.
Measures:
Check that the
configured number of
batteries matches the
actual number.
Check that the actual
number of batteries
meets requirements.
Disconnected the
external battery charger,
check whether the alarm
is cleared. If not,
contact Huawei
technical support for
repair.
0034-01
Remaini
ng cap.
warning
Minor
Automatic
clear
If no action is taken,
continued discharge will
result in system shutdown
due to EOD.
Possible cause:
The battery discharge
lasts too long.
The mains input is
abnormal.
The number of batteries
or battery capacity is
incorrectly set.