A Alarm Handling
Issue 02 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
63
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
bypass input frequency
exceeds the configured
range. If yes, change the
range or wait until the
bypass input recovers.
0011-01
BPS
phase
reverse
Minor
Automatic
clear
If the inverter has not
started, the system has no
output, and inverter
startup is prohibited.
If the inverter has started,
the inverter still works
properly, but the system
cannot transfer to bypass
mode.
Possible cause: The bypass
input three-phase sequence
is incorrect.
Measure: Check that
bypass input power cables
are correctly connected.
0012-01
BPS
neutral
loss
Minor
Automatic
clear
If the inverter has not started,
the system has no output, and
inverter startup is prohibited.
If the inverter has started, the
inverter still works properly,
but the system cannot
transfer to bypass mode.
Possible cause: The bypass
input neutral wire is not
connected.
Measures: Check that
bypass input power cables
are correctly connected.
0014-01
Start
timeout
Critical
Manual
clear/Power
-off clear
The UPS cannot start.
Possible causes:
The bypass load
exceeds the rated
inverter load.
An internal fault occurs
in the UPS.
Measures:
Reduce the output load,
manually clear the
alarm, and restart the
UPS.
Contact Huawei
technical support for
repair.
0020-01
Batt.
reverse
Critical
Automatic
clear
The power supply from the
UPS and system is not
affected.
Possible cause: Batteries
are reversely connected.
Measure: Check the battery
installation, and reinstall
the batteries.
0022-01
No
Minor
Automatic
The power supply from the
UPS and system is not
Possible causes: