TP48200A-HT19C3 and TP48200A-HT19C4 Telecom
Power
User Manual
A Technical Specifications
Issue 03 (2019-11-15)
Copyright © Huawei Technologies Co., Ltd.
87
Item
Specifications
Voltage measurement range
Line voltage: 30-600 V AC
Phase voltage: 20-400 V AC
Continuous overload voltage
800 V AC
Current measurement range
200 mA to 100 A
Single phase power measurement range
0-48000 W/var/VA
Total power measurement range
0-96000 W/var/VA
Frequency measurement range
45-60 Hz
Power factor measurement range
-1 to 1
Current precision
0.5% (10-100 A)
Voltage precision
0.5% (20-400 V); line voltage: 1.0%
Power precision
1.0%
Power factor precision
1.0%
Frequency precision
45-60 Hz
Electric energy precision
1.0% (0.5 C-1-0.5 L)
Operating temperature
-10°C to +50°C
Storage temperature
-25°C to +75°C
Relative humidity
20%-95% RH (non-condensing)
Power input
18-90 V DC
Two options: 85-265 V AC or 85-330 V DC
Power consumption
2 W