TP48200A-HT19C3 and TP48200A-HT19C4 Telecom
Power
User Manual
2 Overview
Issue 03 (2019-11-15)
Copyright © Huawei Technologies Co., Ltd.
17
alarm. The SMU monitors and regulates the temperature control unit based on the temperature
measured by the temperature sensor to ensure the normal operating temperature for the
cabinet.
Figure 2-3
Conceptual diagram
2.5 Configurations
Table 2-1 describes the system configurations for the TP48200A-HT19C3 and
TP48200A-HT19C4.
Table 2-1
Configurations
Item
TP48200A-HT19C3
TP48200A-HT19C4
Application environment
Class C
Temperature control unit (TCU)
Equipment compartment: HXC150S heat exchanger
Battery compartment: TEC
Space for customer equipment
16U
AC input system
220/380 V AC three-phase,
four-wire input system, compatible
with 220 V AC single-phase input
system
110 V AC dual-live wire
AC input circuit breaker
One 3-pole 63 A circuit breaker
One 2-pole 100 A circuit breaker