TP48200A-HT19C3 and TP48200A-HT19C4 Telecom
Power
User Manual
4 Maintenance
Issue 03 (2019-11-15)
Copyright © Huawei Technologies Co., Ltd.
64
Figure 4-12
Removing the fixing plate from the internal circulation fan
4.
Remove the internal circulation fan, as shown in Figure 4-13.
Figure 4-13
Removing the internal circulation fan
Step 4
Install a new internal circulation fan.
1.
Secure the internal circulation fan to the fan fixing plate using screws.
2.
Install the fan fixing plate.
3.
Install the cover for the internal circulation fan.
4.
Connect the removed cables to the internal circulation fan based on the recorded
positions.
Step 5
Connect the transfer terminal.
Step 6
Connect the power cable for the UIM02C.
1.
Reconnect the -48 V power cable to the UIM02C backplane.
2.
Push in the UIM02C and tighten the screws.
3.
Reconnect signal cables to the UIM02C panel based on the recorded positions.
4.
Disconnect the ground cable from the ESD wrist strap, and take off the ESD wrist strap
and ESD gloves.