Remote System

User’s Guide

https://www.b-plus-kk.jp/ E-mail [email protected]

Demensions

Construction of the system

【Function of each Component】

Remote 

 Mounted on a moving side. It transmits CC-Link data to the Base and supplies power to connected CC-Link interface device.

Base 

 Mountes on the fixed side. It transmits CC-Link data to the Remote and supplies power to the Remote inductively through air-gap.

Remote Coupler System

CC-Link version

Remote part :RCD22T-211-CLC
Base part part:RCD22E-211-CLC

*Compatible with CC-Link Ver.1.10/Ver.2.0.

No settings for station type, number of occupied stations, etc. 

are required.

*The  built-in  DIP  switches  can  be  used  only  to  set  the 

communication speed and internal terminating resistor.

*No communication problem even if multiple remote coupler 

system CC-Link specifications are used.

0

1

2

3

4

5

6

7

8

-2

-4

-6

-8

-10

2 4 6 8 10

Y

X

mm

Output current ≦ 2A

Type number

A

(mm)

B

(mm)

C

(mm)

RCD22T-211-CLC

50

45

300

RCD22E-211-CLC

  T312101Oe

2022.11.15

終端
抵抗

CC-Link

ユニット

機器

CC-Link

ユニット

CC-Link

ユニット

CC-Link

ユニット

CC-Link

ユニット

電源

24V DC

終端
抵抗

終端
抵抗

終端
抵抗

CC-Link

ユニット

機器

Remote part

 Base part

The built-in terminating 
resistor SW4 in this 
configuration example 
is set to Base part part 
OFF and Remote part 
ON.

X:Center off set (mm)

Y:Transmitting distance (mm)

LED indication

  Installation

A

B

C

(^_^)

(^_^)

Specifications

Master 

unit

CC-Link 

unit

CC-Link 

unit

CC-Link 

unit

 CC-Link data

Terminator

Power supply

24V DC

Terminator

Power supply

-Design the product so that it can be used under the wiring 

and ambient conditions specified in the specifications. Also, 

design the product to meet the requirements for "transmission 

distance," "axis misalignment," "output voltage," and "output 

current.

Designing  out  of  the  specifications  may  cause  unexpected 

malfunctions, troubles, or failures due to deterioration of internal 

components.
-In  remote  coupler  systems,  the  control  signal  may  become 
unstable outside of specification. If it affects the operation of 
the equipment, start data communication after it is within the 
specification range.

-Be sure to attach the included ferrite clamp (gray) to the communication 

cable and power cable in two turns, and attach the ferrite clamp (white) to the 

communication cable and power cable together in one turn within 20 cm from 

the Base part part and Remote part main unit. Figure 2. (Figure 2) 

Remote:RCD22T-211-CLC

RCD22T-211-CLC

75

90

90

75

97

63

4-φ5.5

4-φ10 depth 6

FG(faston 0.25")

45

30

10

Status LED(Green/Yellow)

Power LED(Green)

Dip-switch

Power

Signal

A66e

RCD22E-211-CLC

75

90

90

75

97

63

4-φ5.5

4-φ10 depth 6

45

30

10

A65e

FG(faston 0.25")

Status LED(Green/Yellow)

Power LED(Green)

Dip-switch

Power

Signal

Base:RCD22E-211-CLC

pin signal(4pin) Power(4pin)

1

SLD

+24V

2

DB

Not use

3

DG

24G

4

DA

Not use

pin signal(4pin) Power(4pin)

1

SLD

+24V

2

DB

Not use

3

DG

24G

4

DA

Not use

Type number

RCD22E-211-CLC

Supply voltage

24 V DC ± 5 %

 (include ripple)

Current consumption

≦ 3 A

Communication

CC-Link data

Communication speed 156kbps....10M bps (Changes by Dip switch)
Data delay max.30bit
Start-up time ≦ 2 sec*

Operating temperature 0...+50 ℃
Connector Signal/ PowerSignal M12/4 pin Male Acoding / M12/4 pin Male Acoding
Available connector cable Signal/Power VA-4DSX5CCG4[5m] / TM-4DSX5HG2-1/3[5m] 
Degree of protection

IP 67

Material Housing

Aluminum anodized finish

Active surface

ABS + PBT

Bundled items

Ferrite core clamp ( Gray x2 / White x1 )

Type number

RCD22T-211-CLC

Output voltage

24V ± 1.5V DC

Output current

≦ 2A

Transmitting distance

3...5mm

Center off-set

± 4mm

Operating temperature 0...+50 ℃
Degree of protection

IP 67

Connector Signal/ Power

M12/4 pin Male Acoding / M12/4 pin Female Acoding

Available connector cable Signal/Power VA-4DSX5CCG4[5m] / TM-4DBX5HG2-1/3[5m])

Material

Housing

Aluminum anodized finish

Active surface ABS + PBT

Bundled items

Ferrite core clamp ( Gray x2 / White x1 )

* This means the time since the timing when a Remote 

part and a Base part are energized within 

 the transmission area until the timing when the 

wireless signal transmission starts. It doesn't mean 

the time until the system as CC-Link established.

Transmitting Area Diagram

(Non-flush mounted)  

[Example : Supply voltage at 24V DC]

* When excessive heat is generated.It stops 

the power supply and once heat cool-down.

RCD22E would be restarted.

LED

Color

LED State

Power LED

Green

ON

The power supply* is supplied. 

Base & 

Remote part

OFF

The power supply* is not supplied. 

Blink

Anomalous temperature(turn on : 9s / turn off : 2s)

Base part

Green

Blink

Supply voltage is low. (turn on : 0.5s / turn off : 0.5s)

Blink

Supply voltage is high. (turn on : 0.1s / turn off : 0.1s)

Remote part Green Blink

Output voltage is low. (turn on : 0.5s / turn off : 0.5s)

Status LED

Yellow ON

Inzone.

Base & 

Remote part Green

ON

Unusual data is received continuously. 

Blink

Interval of blinking varies by the baud rate. (Refer to upper table. )

*Indicates External power supply at Base and indicates Base part at Remote.

When temperature and voltage are abnormalities - - -

LED turned on for 6 sec changes to blink of the interval of 0.5 

sec or 0.1 sec. 

Anomalous TEMP

Anomalous TEMP&Voltage

(0.5 sec interval / Votage low)

6 sec

2 sec

ON
OFF

ON
OFF

-To avoid the influence of surrounding metal and mutual interference between products, 

be sure to open a space larger than the value shown in the table below.(Fig.1)

- When installing a ferrite clamp, be careful not to apply excessive stress 

to the cable due to sudden bending at the connector end or both ends of 

the ferrite clamp.

- Install so that water and cutting water do not get on the end (wiring 

part) of the cable. Moisture is transmitted from the cable core to the main 

body, causing short circuits and corrosion.

-  When  routing  cables  with  bends,  install  them  above  the  bend 

radius of the cables to be used.

Metal facing

( 一 _ 一;) 

(Fig.4)

(Fig.5)

    Foreign material invades inside the sensor

Base part

metal

metal

moisture

Foreign material

- Fix the peripheral cables and install them so that they will not be 

shaken or shocked.
- Use the tab terminal (FG) in a place where the noise environment is bad. (Fig.3)
- To reduce the effect of self-heating, it is recommended to install it on 

metal using case mounting screws.

-  If  foreign  material  get  inside  the  device  from  the  end  of  the 

connector, it may cause fire, smoke, fire, electric shock, or malfunction 

due to malfunction or short circuit.(Fig.5)

- Do not put metal objects between the operating heads.

-  Since  metal  overheating  and  internal  elements  may  be  damaged,  install 

the base so that it does not face the metal before turning on the power. (Fig.4)

(Fig.2)Clamping

(Fig.3)Installation using the tab terminal

(Fig.1)arrange with space

CC-Link unit

CC-Link unit

Setting ferrite core clamp

CC-Link signal

Max.20cm

Ferrite 

core(Gray)

Ferrite 

core(Gray)

Ferrite

core(White)

Power