IPS Test Type
Description
Minimum
underfrequency
(81.S1)
The default underfrequency protection threshold is 49.8 Hz,
and the default protection time threshold is 0.1s.
Minimum
underfrequency
(81.S2)
The default underfrequency protection threshold is 47.5 Hz,
and the default protection time threshold is 0.1s.
Step 3 After the IPS test is complete, IPS State is displayed as IPS state success. Tap
Historical report in the upper right corner of the screen to view the IPS check
report.
----End
7.3 SmartLogger Networking Scenario
See the
Distributed PV Plants Connecting to Huawei Hosting Cloud Quick
Guide (Distributed Inv SmartLogge RS485 Networking)
PV Plants Connecting to Huawei Hosting Cloud Quick Guide (Inv
. You can scan the QR code to obtain it.
Figure 7-18 SmartLogger1000A
Figure 7-19 SmartLogger3000
SUN2000-(3KTL-10KTL)-M1
User Manual
7 Man-Machine Interaction
Issue 02 (2020-11-20)