FusionModule2000 Smart Modular Data Center
Product Description
5 Power Supply and Distribution System
Issue 06 (2020-05-21)
Copyright © Huawei Technologies Co., Ltd.
15
Figure 5-7
Layout of smart module B (NMW, N+1 scenario)
Figure 5-8
Layout of smart module B (NMW, 2N scenario)
Table 5-2
Power distribution specifications
Item
Specifications
Integrated PDF
160 A/250 A power input (IT input circuit breaker and
smart cooling product input circuit breaker), 48 routes for
IT power distribution, 8 routes for smart cooling product
power distribution, and 1 route for lighting power
distribution; supports 95 kW/148.5 kW IT loads.
Precision PDF
160 A/250 A/400 A power input, supports maximum 144
routes for IT power distribution and 95 kW/148.5 kW/235
kW IT loads.
NMW
250 A/400 A power input, supports 123 kW/198 kW IT
loads.