FusionModule2000 Smart Modular Data Center
Product Description
7 Temperature Control System
Issue 06 (2020-05-21)
Copyright © Huawei Technologies Co., Ltd.
135
The water cooling module can be installed in stack mode to maximize the installation
space and reduce the footprint.
The water cooling module uses cooling water for heat exchange to improve the heat
exchange efficiency and improve the energy efficiency of the entire system to 4.0 COP.
Table 7-26
Operating environment specifications with water cooling module
Item
Technical Specifications
Power system
220 V to 240 V AC 1Ph 50 Hz/60 Hz
Refrigerant
R410A
Heat exchanging
capacity
55 kW
Temperature range
4°C to 45°C
Humidity range
5%–90% RH
Storage temperature
–40°C to +70°C
Storage humidity
5%–95% RH (non-condensing)
Inlet water
temperature range of
chilled water
10°C to 37°C
Highest operating
temperature of the
shell pass (°C)
125
Highest operating
temperature of the
tube pass (°C)
60
IP rating
IPX4
Altitude
0–4000 m (derated when the altitude is greater than 1000 m)
Environment
Enclosed indoor environment in which the temperature and
humidity can be controlled within the ranges of 4°C to 45°C and
5% RH to 90% RH respectively. If the indoor installation position
is ventilated, it should be more than 5 km away from the sea or
pollution sources (such as salt lakes, chemical plants, mineral
plants, thermal power plants, and coal mines).
Dimensions (H x W x
D)
330 mm x 326 mm x 1417 mm
Net weight (kg)
60
Certification
CE, RoHS, REACH, WEEE, and Chinese industrial product
manufacture license