6.2.2 Installing the Rectifier (TP48600B, TP481200B)
Prerequisites
The pre-fab. modules have been installed.
The rectifier delivered onsite is complete and intact after unpacking and acceptance. If
any problem is found, contact your local Huawei office.
Preparations
Tool: none
Material: rectifier
Skill requirement: skilled technician
To avoid electric shock, do not put your hands into a rectifier slot.
When a rectifier is running, a high temperature is generated around the air exhaust vent at
the rear. Do not touch the vent or cover the vent with cables or other objects.
Procedure
Step 1
Determining the position of the rectifier
Step 2
(Optional) Remove filler panels from the rectifier installation position based on the
installation requirements.
Step 3
Push the locking latch leftward and pull out the handle.
Step 4
Gently push the rectifier into its slot along the guide rails.
Step 5
Push the handle in place.
Step 6
Push the locking latch downward.
Figure 6-13
Installing the TP48600B rectifier