Possible causes
Procedures
A network connection error
occurs.
Check the network connection.
The IP address is incorrectly set.
Check whether the PC IP address of the U2000 is
consistent with that of the device.
The SNMP protocol is
incorrectly configured.
Check whether the SNMP parameters on the U2000 are
consistent with those on the EDFA.
l
In scenario 2:
Possible causes
Procedures
The network cable is
disconnected.
Check whether the network cable is connected
properly.
The network configurations are
changed.
Check whether the network configurations are correct.
Hardware is faulty.
Contact Huawei technical support engineers.
3.4.2 Common Power Module Faults
Symptom
The indicators are off, the fan does not rotate, and the device cannot run.
Possible causes and procedures
Possible causes
Procedures
The power plug is not properly
connected.
Check the power connector on the device and properly
connect the power connector again.
The voltage is beyond the range
of -72 V to -38.4 V.
Measure the voltage with the multimeter. Connect the
red probe of the multimeter to the ground pin and the
black probe to the -48 V pin. Contact the equipment
room administrator if the voltage tested is beyond the
range of -72 V to -38.4 V.
Hardware is faulty.
Contact Huawei technical support engineers.
3.5 Common Service Module Faults
EDFA0820-D
Routine Maintenance Guide