UPS5000-E-(40 kVA-320 kVA)
User Manual
3 Installation
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
73
----End
3.2.10 Connecting AC Input Power Cables
3.2.10.1 Single Mains
Context
Prepare OT terminals onsite. Strip the cable to expose the copper wire, which should be as
long as the part where the OT terminal is secured with the cable.
Procedure
Step 1
(Optional) Connect cables to the input PDC.
For the connection method, see the
PDC-0630ACV4INA Power Distribution Unit User Manual
. If the
mains input and bypass input share a power source, mains and bypass input terminals are connected by
copper bars.
Step 2
Connect the wires of the AC input power cable to terminals L1, L2, L3, and N on the UPS
cabinet, as shown in
(for the UPS5000-E-120K-F120/UPS5000-E-200K-F200),
(for the UPS5000-E-320K-F320), and
UPS5000-E-320K-F320T).