UPS5000-E-(40 kVA-320 kVA)
User Manual
B Alarm List
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
237
Alarm
ID
(Alarm
ID-Caus
e ID)
Alarm
Name
Severit
y
Cause
Solution
board fault
contact board
MUE05A
I2C
communicati
on fails.
MUE05A.
0090-2
The dry
contact board
MUE06A
I2C
communicati
on fails.
Replace the dry contact board
MUE06A.
0356
Battery
mode
Minor
Battery
mode.
Running status displayed. See
details about how to handle other
alarms.
0359
No power
supplied
Warning
No power
supplied.
Running status displayed. See
details about how to handle other
alarms.
0332
Output
disabled
Minor
The output is
disabled.
Running status displayed. See
details about how to handle other
alarms.
0334
BSC
master
system
Warning
BSC master
system.
Running status displayed. No
suggested measures.
0334
BSC slave
system
BSC slave
system.
Running status displayed. No
suggested measures.
0337
PDC
bypass
input
breaker
open
Critical
The bypass
input circuit
breaker on
the PDC is
OFF.
Running status displayed. No
suggested measures.
0338
PDC output
breaker
open
Critical
The output
circuit
breaker on
the PDC is
OFF.
1.
Check that all UPS output
switches are ON.
2.
On the LCD, check that
PDC
output breaker open
alarm has
disappeared. If the alarm
persists, tap the
Clear Fault
button to clear the alarm.
0341
PDC maint.
breaker
closed
Minor
The
maintenance
circuit
breaker on
the PDC is
Running status displayed. No
suggested measures.