UPS5000-E-(40 kVA-320 kVA)
User Manual
B Alarm List
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
233
Alarm
ID
(Alarm
ID-Caus
e ID)
Alarm
Name
Severit
y
Cause
Solution
abnormal.
The fan
monitorin
g cable
for the
power
module is
abnormal.
0043-2
The fan is
faulty.
Check the fan or replace the bypass
unit or module.
0043-3
The fan is
faulty.
The fan
monitorin
g cable is
faulty.
1.
Replace the fan.
2.
Check the fan monitoring cable.
0043-4
0047-1
Not ready
Critical
The ready
switch is
OFF.
Turn on the ready switch.
0060-4
Inverter
abnormal
Critical
A load
short-circ
uit occurs.
A short
circuit
occurs
inside the
module.
The fault
seldom
occurs.
1.
Check load cable connections.
2.
If load cable distributions are
normal, replace the power
module.
0061-7
Inverter
alarm
Minor
The bypass
waveform is
abnormal.
1.
If not all modules generate the
alarm, start the UPS and transfer
it to normal mode and replace
the faulty module.
2.
If all modules generate the
alarm, open the bypass input
circuit breaker. After the
inverter relay is closed, close
the bypass input circuit breaker
10 seconds later.
0564-1
Overload
timeout
Critical
The load
is
excessive.
Derating
1.
Check that there is no overload.
2.
Check that the module power is
not derated due to a fan fault.
3.
If the alarm persists, replace the