UPS5000-E-(40 kVA-320 kVA)
User Manual
8 Technical Specifications
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
209
Item
UPS5000-E-120K-F
120
UPS5000-E-20
0K-F200
UPS5000-E-32
0K-F320
UPS5000-E-32
0K-F320T
Output
voltage
unbalance
Voltage unbalance: ±3%; phase unbalance: ±2°
Overload
capability
Inverter overload capability:
105% < load ≤ 110%: transfer to bypass mode after 60 min
110% < load ≤ 125%: transfer to bypass mode after 10 min
125% < load ≤ 150%: transfer to bypass mode after 1 min
Bypass overload capability:
Load ≤ 135%: run continuously at 30°C or lower
1000% load: run for 100 ms
8.8 System Electrical Specifications
Item
UPS5000-E-120
K-F120
UPS5000-E-200
K-F200
UPS5000-E-320
K-F320
UPS5000-E-3
20K-F320T
System
efficiency
96%
Redundancy
design
The auxiliary power supplies, centralized controllers, and parallel signals
use redundancy design.
Number of
UPSs
connected in
parallel
≤ 4