UPS5000-E-(40 kVA-320 kVA)
User Manual
B Alarm List
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
238
Alarm
ID
(Alarm
ID-Caus
e ID)
Alarm
Name
Severit
y
Cause
Solution
ON.
0342
Mains
input
breaker
open
Critical
The mains
input circuit
breaker is
OFF.
Running status displayed. No
suggested measures.
0343
BPM input
breaker
open
Critical
The bypass
input circuit
breaker is
OFF.
Running status displayed. No
suggested measures.
0340
Maint.
breaker
closed
Minor
The
maintenance
circuit
breaker is
ON.
Running status displayed. No
suggested measures.
0345
Battery
breaker
open
Critical
The battery
circuit
breaker is
OFF.
Running status displayed. See
details about how to handle other
alarms.
0335
Generator
connected
Warning
The generator
is connected.
Running status displayed. No
suggested measures.
0594-1
Insufficient
redundant
racks
Minor
The load
is
excessive.
The
configure
d number
of
redundant
racks is
incorrect.
1.
Reduce the load.
2.
Decrease the configured number
of redundant racks.
0095-1
Insuffi.
redundancy
Minor
The load
is
excessive.
The
configure
d number
of
redundant
modules
is
incorrect.
1.
Reduce the load.
2.
Decrease the configured number
of redundant modules.
0096-1
ECO volt.
Minor
The ECO
bypass
1.
Check the bypass input voltage
and frequency.