LP-551 Rev. 3.9.16
61
Part 13 - Installation Checklist
Light Off Activities
Date Completed:
1. Fill the Heating System
Check all piping and gas connections.
Verify all are tight.
Pressurize system.
PSI
Add water to prime condensate cup.
Verify near boiler piping is properly
supported.
2. Check Gas Pipe
Leak test using locally approved methods
(consult jurisdictional code book).
Check incoming gas pressure (3.5 to 14”
WC).
Static WC
Check the “drop” on light off (less than 1”
WC).
Dynamic WC
3. Check Combustion
Check and adjust (if necessary) carbon
dioxide content.
%CO2 High Fire
%CO2 Low Fire
Check and adjust (if necessary) carbon
monoxide content.
ppm CO High Fire
ppm CO Low Fire
4. Check Electrical
Connections
Ensure all electrical connections of line
voltage (pumps, etc.) and low voltage
circuits (system sensor, outdoor sensor,
etc.) are properly wired.
5. Verify System Operation
Turn up thermostat to verify wiring
connections.
6. Record Ionization
Current
Check uA reading at d7 on the status
menu (see Start-Up section, this manual).
uA High Fire
uA Low Fire
7. Storage Tank
Verify safety and operation of the storage
tank. Record settings.
DHW Setpoint
DHW Differential
8. Mixing Valve
Ensure thermostatic mixing valve is
properly supported and installed.
9. Convert the Boiler
If necessary, convert the boiler to the
proper fuel type.
Locate the stickers in the appropriate
locations on the boiler.
Verify combustion settings after gas
conversion - Carbon Dioxide.
%CO2 High Fire
%CO2 Low Fire
Verify combustion settings after gas
conversion - Carbon Monoxide.
ppm CO High Fire
ppm CO Low Fire
Mail in conversion registration.
Notes:
Table 33 - Installation Checklist
Allowing the boiler to operate with a dirty combustion
chamber will hurt operation. Failure to clean the heat
exchanger as needed by the installation location could result
in boiler failure, property damage, personal injury, or death.
Such product failures ARE NOT covered under warranty.
In unusually dirty or dusty conditions, care must be taken to
keep boiler cabinet door in place at all times. Failure to do so
VOIDS the warranty.
The boiler requires minimal periodic maintenance under normal
conditions. However, in unusually dirty or dusty conditions,
periodic vacuuming of the cover to maintain visibility of the
display and indicators is recommended.
Periodic maintenance should be performed once a year by a
qualified service technician to assure that all the equipment
is operating safely and efficiently. The owner should make
necessary arrangements with a qualified heating contractor for
periodic maintenance of the boiler. Installer must also inform
the owner that the lack of proper care and maintenance of the
boiler may result in a hazardous condition.
Part 14 - Maintenance Report
Summary of Contents for EP-220 VWH
Page 33: ...LP 551 Rev 3 9 16 33 Figure 24 Cascade Master and FollowerWiring ...
Page 34: ...LP 551 Rev 3 9 16 34 Figure 25 Internal Connection Diagram ...
Page 57: ...LP 551 Rev 3 9 16 57 Figure 30 Combustion System Replacement Parts 220kBTU Model ...
Page 58: ...LP 551 Rev 3 9 16 58 Figure 31 Combustion System Replacement Parts 299 399kBTU Models ...
Page 59: ...LP 551 Rev 3 9 16 59 Figure 32 Replacement Parts All Models ...