LP-551 Rev. 3.9.16
56
It is very important that the condensate piping be no smaller
than ¾”. To prevent sagging and maintain pitch, condensate
piping should be supported with pipe supports, and pitched
¼” per foot to allow for proper drainage. Failure to maintain
proper pipe size and pitch could result in condensate leakage
and potential water damage to property.
The condensate line must remain unobstructed, allowing free
flow of condensate. If condensate freezes in the line, or if line is
obstructed in any other manner, condensate can exit from the
tee, resulting in potential water damage to property.
10. If the boiler has a condensate pump, ensure the pump
operates properly before considering maintenance complete.
Figure 29 - Condensate Detail
Summary of Contents for EP-220 VWH
Page 33: ...LP 551 Rev 3 9 16 33 Figure 24 Cascade Master and FollowerWiring ...
Page 34: ...LP 551 Rev 3 9 16 34 Figure 25 Internal Connection Diagram ...
Page 57: ...LP 551 Rev 3 9 16 57 Figure 30 Combustion System Replacement Parts 220kBTU Model ...
Page 58: ...LP 551 Rev 3 9 16 58 Figure 31 Combustion System Replacement Parts 299 399kBTU Models ...
Page 59: ...LP 551 Rev 3 9 16 59 Figure 32 Replacement Parts All Models ...