HT9022
EN - 48
Range [kW], [kVA]
Resolution [kW], [kVA]
Uncertainty
0.00
÷
99.99
0.01
±
(3.0
%
rdg+3dgt)
100.0
÷
999.9
0.1
Uncertainty defined for: sine waveform > 65Hz, Voltage > 10V, Current
≥
5A,
Pf
≥
0.5
Active Energy
Range [kWh]
Resolution [kWh]
Uncertainty
0.00
÷
99.99
0.01
±
(2.0
%
rdg+3dgt)
100.0
÷
999.9
0.1
Uncertainty defined for: sine wave 10..65Hz, Voltage > 10V, Current
≥
2A,
Pf
≥
0.5
Range [kWh]
Resolution [kWh]
Uncertainty
0.00
÷
99.99
0.01
±
(3.0
%
rdg+3dgt)
100.0
÷
999.9
0.1
Uncertainty defined for: sine waveform > 65Hz, Voltage > 10V, Current
≥
5A,
Pf
≥
0.5
Reactive Power
Range [kVAR]
Resolution [kVAR]
Uncertainty
0.00
÷
99.99
0.01
±
(2.0
%
rdg+3dgt)
100.0
÷
999.9
0.1
Uncertainty defined for: sine wave 10..65Hz, Voltage > 10V, Current
≥
2A,
0.992
≥
Pf
≥
0.5
Range [kVAR]
Resolution [kVAR]
Uncertainty
0.00
÷
99.99
0.01
±
(3.0
%
rdg+3dgt)
100.0
÷
999.9
0.1
Uncertainty defined for: sine waveform > 65Hz, Voltage > 10V, Current
≥
5A,
0.992
≥
Pf
≥
0.5
Reactive Energy
Range [kVARh]
Resolution [kVARh]
Uncertainty
0.00
÷
99.99
0.01
±
(2.0
%
rdg+3dgt)
100.0
÷
999.9
0.1
Uncertainty defined for: sine wave 10..65Hz, Voltage > 10V, Current
≥
2A,
0.992
≥
Pf
≥
0.5
Range [kVARh]
Resolution [kVARh]
Uncertainty
0.00
÷
99.99
0.01
±
(3.0
%
rdg+3dgt)
100.0
÷
999.9
0.1
Uncertainty defined for: sine waveform > 65Hz, Voltage > 10V, Current
≥
5A,
0.992
≥
Pf
≥
0.5
Power factor
Range Resolution
Uncertainty
0.20
÷
1.00
0.01
±
3°
Uncertainty defined for: sine waveform 10..65Hz, Voltage > 10V, Current
≥
2A
Uncertainty defined for: sine waveform > 65Hz, Voltage > 10V, Current
≥
5A
Voltage and Current harmonics
Harmonic order
Frequency [Hz]
Resolution [V], [A]
Uncertainty
1
÷
25
10
÷
75
0.1
±
(5.0
%
rdg+5dgt)
1
÷
8
75
÷
400
Phase sequence and 1-lead phase coincidence
Range Input
impedance
100
÷
1000V
1.3M
Ω
Frequency range: 40..70Hz.
(*) Measurement carried out under the following standard conditions: instrument firmly held in the hand, standard shoes, standard floor,
etc.
www.
.com
1.800.561.8187