Chapter 10 Parameter
Shenzhen Hpmont Technology Co., Ltd.
-76-
HD09 Series User Manual V1.1
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
F09.10
Compensation filtering
time for motor transfer
0.01 - 10.00s
0.10s
0.01s
○
F09.11
Differential compensation
for motor differential
0.0 - 250.0%
200.0%
0.1%
×
F09.12
The time constant of the
motor compensation
0.1 - 25.0s
2.0s
0.1s
○
F09.14
AVR (automatic voltage
regulation) function
0: No action
1: Keep acting
2: No action only in Dec.
1
1
○
F09.15
Oscillation-suppression
mode
0: Oscillation-suppression mode 1
1: Oscillation-suppression mode 2
0
1
○
F09.16
Oscillation-suppression
coefficient
0 - 200
50
1
○
F15: Digital Input / Output Terminals Parameter
F15.00
DI1 function
0: Unused
1: Inverter enabled
2,3: FWD / REV function
4: Three-wire operation mode
8: AI to be the frequency source
11: Terminal control mode to be the run
command source
13 - 15: Multi-step frequency terminal
1 - 3
17: Frequency ramp (UP)
18: Frequency ramp (DN)
19: Clearing auxiliary frequency setting
20,21: Forward and reverse jog
command control input (JOGF / JOGR)
26,27: Selection terminals in Ace. and
Dec. time 1, 2
41: Coast to stop (normally-open input)
42: Coast to stop (normally-closed
input)
44: External fault signal (normally-open
input)
2
1
×
F15.01
DI2 function
3
1
×
F15.02
DI3 function
0
1
×