Chapter 7 Detailed Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
-46-
HD09 Series User Manual V1.1
Ref. Code
Function Description
Setting Range [Default]
F17.05
Communication error detection time
0.0 - 1000.0 [0.0s]
When the communication error occurs more than F17.05, reported E0029 failure (SCI communication error),
the inverter continues to run.
•
F17.05 = 0, the inverter does not detect communication error.
F17.09
Communication write function parameter saving EEPROM choice
00 - 11 [01]
Used to select communication modification parameter, whether it is stored in the EEPROM.
Bits: Except of F00.13, F19.03 function parameter, communication EEPROM storage options
Ten: F00.13, F19.03 function parameter communication EEPROM storage options
0: Not save.
1: Save.
Note:
1. When ten = 1, it may damage the inverter. Please exercise caution.
2. Only when using the communication function parameters, the function code is 0x06 or 0x10 is valid, see Chapter
9 MODBUS communication protocol.
F17.10
Network communication timeout detection time
0.0 - 1000.0 [0.0s]
The frequency converter reports that E0028 is faulty (SCI communication time-out) after the interval
between two received correct data (including local or non-local) continues to exceed F17.10.
•
F17.10 = 0, do not detecte fault time.