Shenzhen Hpmont Technology Co., Ltd.
Chapter 7 Detailed Function Introduction
HD09 Series User Manual V1.1
-51-
Input voltage selection (F19.39)
Ref. Code
Function Description
Setting Range [Default]
F19.39
Input voltage selection
00 - 12 [00]
Bits: Model 380V input voltage selection
•
0: 380 - 460V.
•
1: 260 - 460V.
•
2: 200 - 460V.
Ten: Model 220V input voltage selection
•
0: 200 - 240V.
•
1: 140 - 240V.
Note: Low voltage input, the inverter needs to derate the use, the actual output current does not exceed the rated
output current of the inverter.
LCD back screen display (F19.44)
Ref. Code
Function Description
Setting Range [Default]
F19.44
LCD display time
0.0 - 999.9 [5.0min]
Defines the display time of keypad LCD backlight when there is no operation.
•
Normally on in 0.
•
Normally on in fault.
•
In no fault, more than F19.44 time, LCD backlight will be off. If any button press operation panel at this
time, only to open the backlight and not execute the command.