Chapter 6 Operation
Shenzhen Hpmont Technology Co., Ltd.
-26-
HD09 Series User Manual V1.1
6.4
Terminal Control Running
When the terminal controls the operation (F00.11 = 1), the inverter can be started and stopped directly
with the terminal, and the running frequency and the motor running direction.
As follows:
1. After wiring as shown below, turn on the input power.
2. Set the command channel to terminal control (F00.11 = 1).
3. Set the AI setting frequency (F00.10 = 3, F16.01 = 2).
3. Set DI1 terminal forward (F15.00 = 2), DI2 terminal reverse (F15.01 = 3).
4. Set the motor parameters according to the motor nameplate: F08.00 (rated power), F08.01 (rated
voltage), F08.02 (rated current), F08.03 (rated frequency), F08.04 (rated speed).
6. Set acceleration / deceleration time: F03.01 (acceleration time), F03.02 (deceleration time).
7. When the K1 is closed, the motor is running; When K2 is closed, the motor is running in reverse.
8. K1, K2 are closed or disconnected at the same time, the inverter stops.
6.5
Communication Control Operation
In communication control operation (F00.11 = 2), the function parameters, state parameters, and
control commands of the converter can be read and written by the host computer.
In communication, converter is in the slave mode.
Please see section 4.4 External Keypad or Upper Computer, page 17.
For details, see Chapter 9 MODBUS Communication Protocol, page61.
For specific settings, see section 9.6 Application Examples, page 68.
DI1
K1
K2
DI2
GND
HD09
+10
AI
GND