• T-15 Torx screwdriver (for the system board screws)
• T-20 Torx screwdriver (for the processor socket screws)
• Alcohol wipe
Procedure
1.
2.
Remove all power:
a. Disconnect each power cord from the power source.
b. Disconnect each power cord from the server.
3.
Remove the server from the rack.
4.
Remove all power supplies (
Removing and replacing the AC power supply).
5.
6.
Do one of the following:
•
• Remove the 4LFF midplane cage (
Removing and replacing a 4LFF midplane cage).
7.
Remove the primary or secondary PCIe riser cage (
Removing and replacing the primary or secondary PCIe riser
8.
If installed, remove the tertiary PCIe riser cage (
Removing and replacing the tertiary PCIe riser cage).
9.
Remove the FlexibleLOM (
Removing and replacing the FlexibleLOM).
10. Remove all DIMMs (Removing and replacing a DIMM).
11. Remove the fan cage (Removing and replacing the fan cage).
12. Disconnect all cables from the system board.
13. Allow the existing heatsink to cool.
14. Remove the heatsink:
CAUTION: To prevent mechanical damage or depositing oil on your hands or other contaminant to the
heatsink contact surface, hold the heatsink only by the edge of its base plate. Do not touch the heatsink fins.
CAUTION: Heatsink screws must be tightened and loosened in alternating sequence. Do not overtighten the
screws as this might damage the system board or the processor socket.
a. Use a T-20 Torx screwdriver to loosen the captive screws in the sequence specified on the heatsink label.
b. Lift the heatsink away from the system board.
92
Removal and replacement procedures
Summary of Contents for ProLiant DL385 Gen10
Page 30: ...30 Customer self repair...
Page 31: ...Customer self repair 31...
Page 32: ...32 Customer self repair...
Page 129: ...8LFF front panel 12LFF front panel Midplane box LFF only Component identification 129...
Page 142: ...Boxes 2 and 3 to SAS Expander All boxes to SAS Expander 142 Cabling...
Page 143: ...Cable routing Midplane 4LFF SAS SATA drive option Cabling 143...
Page 145: ...Cable routing Rear 3LFF SAS SATA drive option for system board Cabling 145...
Page 147: ...Cable routing Front 2SFF NVMe side by side drive options Cabling 147...
Page 149: ...Cable routing Front 8SFF NVMe drive options Box 1 Box 2 Cabling 149...
Page 150: ...Box 3 150 Cabling...