Cabling and powering up the chassis
Cabling the chassis
After all system hardware is installed, cable the components.
WARNING:
To reduce the risk of electric shock or injury due to high-current electrical energy, be sure that all
power is completely disconnected at the source before beginning any power connections to the
power bus bars or power bus box.
WARNING:
Be sure that all circuit breakers are locked in the off position before connecting any power
components.
CAUTION:
To avoid damaging the fiber cables, do not drape cables from one side of the rack to the other and
do not run cables over a hard corner or edge.
Procedure
1.
Connect the network cables to the Ethernet ports on the I/O module (
I/O module components
on
page 14).
2.
Connect a network cable to the iLO connector on the management module (
Management module
components
on page 13).
3.
Connect the APM cable to the APM connector on the management module (
Management module
components
on page 13).
Installing the cable management arm
IMPORTANT:
If you need to hinge the cable management arm on the rear right-hand side of the rack, see the
instructions in "
Converting the cable management arm for opposite side mounting
on page
38." Perform these steps to convert the arm to a right-hand swing and install the arm on the right
side of the rack.
Procedure
1.
Install the rack rail brace.
36