2.
Connect the supplied 2m SAS cables from the head server unit to the first disk enclosure, as
follows:
•
RAID card 1, port 2 to Drawer 2, I/O module B, port 2
•
RAID card 1, port 1 to Drawer 1, I/O module A, port 1
3.
Connect the supplied 0.5m SAS cables as follows:
•
Drawer 1, I/O module A, port 2 to Drawer 2, I/O module A, port 1
•
Drawer 2, I/O module B, port 1 to Drawer 1, I/O module B, port 2
Figure 9 Cabling the first disk enclosure
RAID card 1, port 2 to Disk enclosure 1, Drawer 2, I/O Module B, Port 2
2m SAS cable
1.
RAID card 1, port 1 to Disk enclosure 1, Drawer 1, I/O Module A, Port 1
2m SAS cable
2.
Drawer 1, I/O module A, port 2 to Drawer 2, I/O module A, port 1
0.5m SAS cable
3.
Drawer 2, I/O module B, port 1 to Drawer 1, I/O module B, port 2
0.5m SAS cable
4.
4.
If you are installing a second disk enclosure:
The cabling for the second disk enclosure is identical to the cabling for the first disk enclosure,
except it is connected to the second RAID card in slot 4.
Connect the supplied 2m SAS cables from the head server unit to the first disk enclosure, as
follows:
•
RAID card 2, port 2 to Drawer 2, I/O module B, port 2
•
RAID card 2, port 1 to Drawer 1, I/O module A, port 1
Connect the supplied 0.5m SAS cables as follows:
•
Drawer 1, I/O module A, port 2 to Drawer 2, I/O module A, port 1
•
Drawer 2, I/O module B, port 1 to Drawer 1, I/O module B, port 2
26
Installing and cabling the HP StoreOnce 4900 Backup system
Summary of Contents for StoreOnce 4900 Backup
Page 47: ...Figure 20 Network configuration flowchart Before running net set wizard 47 ...
Page 98: ...98 Configuring backup servers to work with HP StoreOnce ...
Page 101: ...iSCSI Initiator optional VTL only 101 ...
Page 116: ...Reboot the host Linux system and the connection will work again 1 16 Troubleshooting ...