2.
Select the appropriate storage system in the Navigation pane.
The Initialized Storage System Properties window for the selected storage system opens.
3.
Click
Shut down
.
The Shutdown Options window opens.
4.
Under System Shutdown click
Power Down
. If you want to delay the initiation of the shutdown,
enter the number of minutes in the Shutdown delay field.
The controllers complete an orderly shutdown and then power off. The disk enclosures then power
off. Wait for the shutdown to complete.
5.
If your management server is an SMA and you are not using it to manage other storage arrays,
shut down the SMA. From the SMA user interface, click
Settings > Maintenance > Shutdown
.
Starting the storage system
To start a storage system, perform the following steps:
1.
Verify that each fabric Fibre Channel switch to which the HSV controllers are connected is powered
up and fully booted. The power indicator on each switch should be on.
If you must power up the SAN switches, wait for them to complete their power-on boot process
before proceeding. This may take several minutes.
2.
If the management server you shut down is an SMA, power it on and wait for it to completely
boot. Verify the SMA is running by logging into it using the web interface.
NOTE:
Before applying power to the rack, ensure that the power switch on each HSV controller is
off.
3.
Power on the circuit breakers on both EVA rack PDUs. Verify that all drive enclosures are operating
properly. The status indicator and the power indicator should be on (green).
4.
Wait three minutes and then verify that all disk drives are ready. The drive ready indicator and
the drive online indicator should be on (green).
5.
Power on the upper controller. It takes the role of master controller.
6.
Wait 10 seconds and then power on the lower controller. It takes the role of slave controller.
7.
Verify that the Operator Control Panel (OCP) display on each controller displays the storage
system name and the EVA WWN.
8.
Start HP Command View EVA and verify connection to the storage system. If the storage system
is not visible, click
HSV Storage Network
in the Navigation pane, and then click
Discover
in the
Content pane to discover the array.
NOTE:
If the storage system is still not visible, reboot the management server to re-establish the
communication link.
9.
Check the storage system status using HP Command View EVA to ensure everything is operating
properly. If any status indicator is not normal, check the log files or contact your HP-authorized
service provider for assistance.
HP StorageWorks 6400/8400 Enterprise Virtual Array user guide
51