B-19
Battery Runtime
20º C (68º F) or above
New battery
15 minutes over battery lifetime
15 minutes over full temperature range
Battery Recharge
Time
< 14 Hours (UPS OFF)
< 24 Hours (UPS Operating)
Optimum Battery
Lifetime (25º C/77º F)
3.5 to 5 years
Environmental Specifications
Operating
Temperature
5º to 40º C (41º to 104º F)
15% - 80% relative humidity (non-condensing)
Storage Temperature
-30º to 50º C (-20º to 122º F) Battery life is shortened severely
when temperature exceeds 25º C (77º F) for extended periods.
5% - 80% relative humidity (non-condensing)
Operating Altitude
3000 meters (10,000 ft.)
Storage Altitude
4572 meters (15,000 ft.)
Physical Specifications
Electronics Unit
Dimensions
Packaged:
Height - 41.0 cm (16.0 inches)
Width - 57.0 cm (22.5 inches)
Depth - 72.0 cm (28.4 inches)
Weight - 90.0 kg (198 lbs)
Dimensions
Unpackaged:
Height - 25.5 cm (10.0 inches) - 6 EIA rack units
Width - 42.5 cm (17.0 inches)
Depth - 61.0 cm (24.0 inches)
Weight - 84.0 kg (185.0 lbs)
Minimum Required Service Access Space:
Rear:
Side:
Front:
76.0 cm (30.0 inches)
0.0 cm (0.0 inches)
91.0 cm (36.0 inches)
Table B-23.
A2996A PowerTrust UPS Specifications
. (Continued)
Description
Specification
Summary of Contents for 3000/9x9KS Series
Page 10: ...x ...
Page 38: ...A 4 Figure A 1 Space Planning Grid Sheet ...
Page 39: ...A 5 Figure A 2 System Cutouts ...
Page 70: ...B 28 ...
Page 75: ...C 5 Figure C 3 Space Planning Grid ...
Page 76: ...C 6 Figure C 4 K Class Equipment Profiles ...
Page 77: ...C 7 Figure C 5 T Class Equipment Profiles ...
Page 82: ...C 12 ...