22
Advanced User Instructions
430294ENG-Jun02
Note: The room station should be placed in the
room that most accurately represents the
temperature of the building. Thermostatic
radiator valves when fitted properly should only
serve to deregulate foreign heat sources and
therefore should be fully open. During the
regulation phase all foreign heat source should
be switch off and ventilation should be kept to a
minimum so as not to disturb the regulation
process.
When the heating curve is correctly set the room
temperature should remain constant regardless
of outside temperature. If automatic adaption is
set in the service level the value will blink and is
constantly corrected. In this case it must not be
manually altered.
Recommended values:
Floor heating:
0.3 ….. 1.0
Radiator heating:
1.2 ….. 2.0
Convection heating: 1.5 ….. 2.0
Heating curve graph
Room temperature
compensation
1 2
Works setting: 0.0K
Range: -2.5K … +2.5K
Change with or
1 – Room temperature
2 – Correction
With this parameter it is possible to calibration
the room temperature by ± 2.5K.
Reset function
With this function it is possible to reset all the
room level parameters back to their factory
settings with the exception of burner hours run
and burner starts.
To reset room level parameters hold and
Simultaneously until the following display
appears
Parameters reset
Default screen
Max 80ºC
Min 31ºC
Outside temperature ºC
Boiler
Flow
Temp
ºC