Advanced User Instructions
11
Room temperature correction for PARTY and
HEATING with variable temperature
parameter enabled.
For operating types:
-
PARTY
-
HEATING
The room temperature is set to automatic works
setting of 20ºC or the corrected value which has
been set in the user level.
The actual room temperature values for each of
these two operating types can be set
independently to the automatic program if the
relevant parameter has been enabled in the
service level by an engineer.
The value is set separately when calling up the
operating type PARTY or HEATING by using
the and keys. These values remain
stored for each further call of this operating
type.
Time Clock Programming
It is possible to program up to three cycles /
periods for each desired weekday.
1 – Heating Cycle
For heating each of these cycles has an on / off
as well as a temperature indication for this time
span. The temperature can only be adjusted if
the relevant parameter is enabled in the service
level. Between heating cycles the room
temperature is regulated according to the
night temperature.
2 – Hot Water Cycle
For hot water each of these cycles has an on /
off time. Between hot water cycles hot water
heating is switch off. The temperature is set in
the room level and cannot be changed for each
cycle.
Entering the time clock level
Entering this level is achieved by simply pressing
the
key. The program 1, 2 or 3 which is set
in the room level is shown.
Press key
Boiler circuit
Works setting
program 2
or
Boiler circuit
Room level set to
program 1
or
Boiler circuit
Room level set to
program 3
With the and the heating or hot water
circuit can be called up and is available for
programming.
Calling up of heating cycles
With a further pressing of the
key the first
heating cycle of the selected program shows
complete with indication of weekday, cycle
number, on time, off time and temperature. Each
value is called up with the key in series
-
On time
-
Off time
-
Temperature
The key can be used to step backwards.
The current value which can be changed with
the and keys is shown blinking. Switch
times can be altered in 5 minute intervals and
temperatures in 0.5K increments in the range of
5-30ºC.
The next heating cycle can be called up by
pressing the
key and the process repeated.
Note: The on/off times of not used heating cycles
should be set to 00:00 by simultaneously
pressing the and keys.
The 00:00 value does
not
refer to a clock
time but only shows an undefined switch
time.
After programming the last heating cycle
(Sunday – cycle 3) the first heating cycle
(Monday – cycle 1) will follow.