56
4 214 283 / 00
OVERVIEW OF SETTINGS
FAULT REPORTING OVERVIEW TopTronic
®
T
Status
Designation
Fault type
Code
Remark
System
External sensor
Interruption
10-0
System
External sensor
Short-circuit
10-1
System
Boiler sensor
Interruption
11-0
System
Boiler sensor
Short-circuit
11-1
System
Flow sensor 1
Interruption
12-0
MC1=off, YK1=no current
System
Flow sensor 1
Short-circuit
12-1
MC1=off, YK1=no current
System
Storage sensor
Interruption
13-0
System
Storage sensor
Short-circuit
13-1
System
VE 2
Interruption
14-0
System
VE 2
Short-circuit
14-1
System
VE 2
Alarm
14-7
System
VE 3
Interruption
15-0
System
VE 3
Short-circuit
15-1
System
VE 3
Alarm
15-7
System
VE 1
Interruption
16-0
System
VE 1
Short-circuit
16-1
System
VE 1
Alarm
16-7
System
Solar tank sensor
Interruption (KSPF)
17-0
System
Solar tank sensor
Short-circuit (KSPF)
17-1
System
Flow sensor 2
Interruption
18-0
MC2=off, YK2=no current
System
Flow sensor 2
Short-circuit
18-1
MC2=off, YK2=no current
System
Collector sensor
Interruption (KVLF)
19-0
System
Collector sensor
Short-circuit (KVLF)
19-1
System
Room sensor (RS)
Interruption
20-0
System
Room sensor (RS)
Short-circuit
20-1
System
Burner 1
No switching off (1 min)
30-2
With par. log. alarm can be switched off
System
Burner 1
No switching on (10 min)
30-3
With par. log. alarm can be switched off
System
Burner 2
No switching off (1 min)
31-2
With par. log. alarm can be switched off
System
Burner 2
No switching on (10 min)
31-3
With par. log. alarm can be switched off
System
Exhaust gas temperature
Exceeding
33-5
System
Exhaust gas temperature
SLT triggered
33-8
System
Cleaning stage 1
Triggering by date
40-1
System
Cleaning stage 1
Triggering by interval
40-2
System
Cleaning stage 1
Triggering by counter
40-4
System
Maintenance stage 1
Triggering by date
41-1
System
Maintenance stage 1
Triggering by interval
41-2
System
Maintenance stage 1
Triggering by counter
41-4
System
Cleaning stage 2
Triggering by date
42-1
System
Cleaning stage 2
Triggering by interval
42-2
System
Cleaning stage 2
Triggering by counter
42-4
System
Maintenance stage 2
Triggering by date
43-1
System
Maintenance stage 2
Triggering by interval
43-2
System
Maintenance stage 2
Triggering by counter
43-4