54
4 214 283 / 00
OVERVIEW OF SETTINGS
MAIN SUPPLY
Par.
Designation
Factory
10
Lev.
1
0 %/ K
HF
2
PI-scanning time Ta
20 s
HF
3
PI -reset time Tn
600 s/ °C
HF
CASCADE
Par.
Designation
Factory
10
Lev.
1
Switch-off difference
3 K
OEM
2
Connecting delay
20
OEM
3
Switch-off delay
5
OEM
4
Switching output stage sequence
65
OEM
5
Stage reversal
OFF
OEM
6
Control stage
1
BE
7
Peak load stage
OFF
OEM
8
Group switch-over
OFF
OEM
9
DHW fast activation
OFF
OEM
10
Peak load elevation
10 K
OEM
BUS
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
Bus address central device
10
HF
2
Bus right RS direct circuit
1
HF
3
Bus right RS mixer circuit 1
1
HF
4
Bus right RS mixer circuit 2
1
HF
BUFFER
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
Minimum temperature
5/ 20 °C
HF
2
Maximum temperature
95 °C
HF
3
Temperature elevation, H-GEN
8/ 10/ 12K
HF
4
Switching difference
2/ 5/ 10K
HF
5
Forced discharge
OFF
HF
6
Skimming function switch-on difference
10 K
HF
7
Skimming function switch-off difference
5 K
HF
8
Start-up protection
OFF
HF
9
Discharge protection
OFF
HF
10
Buffer mode of operation
2/ 3
HF
11
Pump follow-on time
3 min
HF
12
Switch-off reference value temp.
70 °C
HF
13
H-GEN release temp. skimming function
60 °C
HF