Type
Maximum output
Minimum output
t
VL
°C
t
Q
°C
Q
h
kW
P
kW
COP
Q
h
kW
P
kW
COP
25
-14
49.1
19.3
2.6
25.8
7.3
3.6
-7
64.2
19.8
3.3
31.7
6.9
4.6
2
84.7
20.5
4.1
40.2
6.7
6.0
7
96.9
20.9
4.6
45.3
6.8
6.7
10
102.2
21.1
4.8
47.4
6.8
7.0
18
114.9
21.6
5.3
54.2
6.7
8.1
30
-14
50.6
21.7
2.3
29.8
9.2
3.2
-7
65.0
22.0
3.0
36.9
8.8
4.2
2
84.7
22.6
3.7
47.4
8.8
5.4
7
96.4
23.1
4.2
53.6
8.8
6.1
10
101.5
23.3
4.4
56.2
8.9
6.3
18
113.8
23.8
4.8
63.6
8.7
7.3
35
-14
52.3
24.6
2.1
25.1
8.7
2.9
-7
65.9
24.6
2.7
30.4
8.2
3.7
2
84.8
25.1
3.4
38.1
8.0
4.7
7
96.1
25.6
3.8
42.8
8.0
5.3
10
101.1
25.8
3.9
44.7
8.0
5.6
18
112.9
26.3
4.3
51.4
8.0
6.4
40
-14
54.0
27.6
2.0
25.0
9.8
2.6
-7
67.0
27.5
2.4
30.0
9.3
3.2
2
85.0
27.8
3.1
37.3
9.1
4.1
7
96.0
28.3
3.4
41.9
9.1
4.6
10
100.8
28.6
3.5
43.8
9.1
4.8
18
112.4
29.0
3.9
50.4
9.0
5.6
45
-14
55.9
30.9
1.8
24.9
11.2
2.2
-7
68.2
30.6
2.2
29.7
10.7
2.8
2
85.5
31.0
2.8
36.8
10.5
3.5
7
97.3
31.5
3.1
41.2
10.4
4.0
10
100.7
31.8
3.2
43.0
10.4
4.1
18
111.9
32.3
3.5
49.7
10.3
4.8
50
-7
69.5
34.1
2.0
29.6
12.3
2.4
2
86.2
34.5
2.5
36.5
12.1
3.0
7
96.4
35.1
2.8
40.8
12.1
3.4
10
100.9
35.4
2.9
42.6
12.1
3.5
18
112.1
36.0
3.1
49.3
11.9
4.1
54
2
87.0
38.5
2.3
36.4
14.1
2.6
7
96.7
38.7
2.5
40.6
14.0
2.9
10
101.1
39.0
2.6
42.4
14.0
3.0
18
112.3
39.8
2.8
49.2
13.8
3.6
Performance data – heating
Belaria
®
fit (85)
Data according to EN 14511
t
VL
=
heating flow temperature (°C)
t
Q
=
source temperature (°C)
Q
h
=
heat output at full load (kW), measured in accordance with
standard EN 14511
P
=
power consumption for the overall unit (kW)
COP
=
Coefficient of performance for the overall unit in accordance
with standard EN 14511
Output correction factors in silenced mode
Silent
Supersilent
Heat output factor
0.95
0.90
Power consumption factor
0.95
0.90
COP factor
1.00
1.00
Q
k
[kW]
Q
k
[kW]
Q
k
[kW]
Q
k
[kW]
68
4 221 546 / 00
GEnERal TECHnICal DaTa