SERVICE - TEMPERATURE COMPENSATION
Press
or
to select:
COOL MODE
HEAT MODE
The water temperature is adjusted based on the outdoor temperature T4.
COOLING
The following parameters can be adjusted:
•
T4_cool_1 (15~30 ºC)
•
T4_cool_2 (35~45 ºC)
•
offset_c (0~15 ºC)
HEATING
The following parameters can be adjusted:
•
T4_heat_1 (-10~10 ºC)
•
T4_heat_2 (15~30 ºC)
•
offset_h (0~30 ºC)
T4_cool _1 T4_cool _2
of f set _c
Tws
T4
Tws'
T4_heat _1 T4_heat _2
Tws
off set _h
T4
Tws'
menu USER - SNOW- BLOWING SWITCH
If enabled, the function activates the fans in order to avoid the accumulation
of snow.
The fans start for 2 minutes every 30 minutes. With T air < 3 °C and unit
stopped.
36
4 221 546 / 00
ConTRol