Type
Maximum output
Minimum output
t
VL
°C
t
Q
°C
Q
k
kW
P
kW
EER
Q
k
kW
P
kW
EER
7
15
67.6
13.5
5.0
22.7
3.4
6.7
20
64.5
15.2
4.3
21.3
3.8
5.6
25
61.3
16.9
3.6
20.0
4.2
4.7
30
58.2
18.7
3.1
18.6
4.8
3.9
35
55.0
20.8
2.6
17.1
5.3
3.2
40
51.8
22.4
2.3
15.7
5.9
2.6
44
48.5
24.4
2.0
14.1
6.6
2.1
10
15
74.2
13.6
5.5
24.6
3.4
7.3
20
70.9
15.3
4.6
23.2
3.7
6.2
25
67.6
17.2
3.9
21.7
4.2
5.2
30
64.2
19.0
3.4
20.2
4.7
4.3
35
60.7
20.9
2.9
18.6
5.3
3.5
40
57.2
22.9
2.5
17.0
6.0
2.9
44
53.7
25.0
2.2
15.3
6.7
2.3
12
15
78.8
13.7
5.8
26.0
3.3
7.9
20
75.4
15.5
4.9
24.5
3.7
6.6
25
72.0
17.2
4.2
22.9
4.2
5.5
30
68.3
19.2
3.6
21.3
4.7
4.5
35
64.7
21.2
3.1
19.7
5.3
3.7
40
61.0
23.3
2.6
17.9
6.0
3.0
44
57.2
25.3
2.3
16.1
6.7
2.4
15
15
86.2
13.8
6.3
28.0
3.2
8.8
20
82.4
15.7
5.3
26.4
3.6
7.3
25
78.6
17.5
4.5
24.7
4.1
6.0
30
74.7
19.6
3.8
23.0
4.7
4.9
35
70.7
21.6
3.3
21.2
5.3
4.0
40
66.8
23.7
2.8
19.3
6.0
3.2
44
62.7
25.8
2.4
17.3
6.7
2.6
18
15
93.8
15.1
6.2
30.7
3.8
8.1
20
89.7
17.2
5.2
29.4
3.9
7.5
25
85.6
19.3
4.4
27.5
4.5
6.1
30
81.4
21.6
3.8
25.6
5.2
5.0
35
75.6
22.7
3.3
23.7
5.9
4.0
40
72.6
26.1
2.8
21.5
6.7
3.2
44
68.3
28.6
2.4
19.3
7.6
2.6
20
15
99.0
15.2
6.5
27.9
3.4
8.1
20
94.7
17.3
5.5
30.9
3.8
8.1
25
90.3
19.5
4.6
28.9
4.4
6.6
30
85.9
21.7
4.0
27.0
5.1
5.3
35
81.3
24.1
3.4
25.0
5.9
4.3
40
76.7
26.4
2.9
22.7
6.7
3.4
44
72.0
28.8
2.5
20.4
7.6
2.7
Performance data – cooling
Belaria
®
fit (53)
Data according to EN 14511
t
VL
=
cooling water flow temperature (°C)
t
Q
=
source temperature (°C)
Q
k
=
cooling capacity at full load (kW), measured in accordance with
standard EN 14511
P
=
power consumption for the overall unit (kW)
EER =
Energy Efficiency Ratio for the overall unit in accordance with
standard EN 14511
Output correction factors in silenced mode
Silent
Supersilent
Cooling capacity factor
0.90
0.85
Power consumption factor
1.00
1.00
EER factor
0.90
0.85
Q
h
[kW]
Q
h
[kW]
Q
h
[kW]
66
4 221 546 / 00
GEnERal TECHnICal DaTa