Hotset GmbH
159
Start-up-, Service- and Operation Manual hotcontrol cDT+
Rev. 1.00.05
Subject to technical changes
Identified faults in header
Possible reason of error
Instructions for trouble shooting
Sensor reversed polarity
Sensor with reversed polarity con-
nected.
Check the pin assignment of connecting
cable and of mold.
Sensor defective or no sensor
connected
No sensor connected, sensor defec-
tive
Check the connected sensors
1) Remove connecting cable of Hot Run-
ner Controller
2) Measure resistance of sensor with
multimeter
3) Infinite resistance means, no sensor
existing or sensor defective
Sensor defective or no sensor
connected
Sensor wrong connected
Check the pin assignment of connecting
cable and of mold.
Sensor permuted
The sensor or the heating of the zone
was connected to the connection of
zone XXX
Check other zones for occurrence of
same fault and remove wiring faults in
connecting cable and mold.
Check not completely execut-
ed!
Check not completely executed!
Repeat MoldCheck for these zones