PAGE 16
14 MAY 2002
CH. 3
MAN0484-01
e. The following screen appears.
Figure 3.6 - JCM200 Configuration Program
Standard Configuration
The JCM200 has a fixed number of 8 %Qs, 8 %Is, and 11 %AQs.
Type:
Displays the register types assigned to the module.
Starting Register:
Denotes the starting location of the register type.
These are user-editable fields.
Ending Register:
Denotes the ending location of the register type. These fields are
automatically
updated
by the Configurator.
Number:
Indicates the quantity of a particular register type. These fields are
automatically updated
by
the Configurator.
Scan Setup
focuses on %AI register
configuration. The
ending register location
and number of registers
for %AIs varies
depending on the register
map.
If you want to add a %AI
register, enter a Starting
%AI Register number.
Then, press
Add
.
To
Delete
a %AI register,
double-click the item, and
a screen appears
allowing you to delete the
register.
Standard Configuration
focuses on 3 register types:
%Q, %AQ, %I. These types
have a fixed number of
registers.
This screen is used to
map the OCS %AI
registers that contain
parameter values from
Engine Control Modules.
This portion of the
screen is used to create
a %AI register map to
depict %AI registers that
have been added.
%AIs listed here can be
double-clicked to delete /
edit them.