U2-S MODEL COMBINATION VIEWING HEAD AND SIGNAL PROCESSOR
15
32-00015—05
7.
Use your light source to generate flamecounts of
between 1200 and 2000 in the signal processor.
Note the flamecount.
a. Increase the gain and store the setting. Confirm
the flamecount increased.
b. Decrease the gain and store the setting. Confirm
the flamecount decreased.
8.
Restore all original settings as recorded in setup and
reconnect the signal processor to the safety system.
Product Decommissioning
When required, decommissioning of the U2-S
flamescanner should be performed in accordance with
requirements of the overall safety system.