Repairs, Replacements and Upgrades
MAN0984_Iss 4_01/19
Touchpoint Plus
Pt. No. 3011M5001
121
Technical Handbook
11)
Switch power on and restore TPPL to normal operation.
Touch the power icon to check battery power levels.
Battery On/Off Switch and Battery Connector
Note:
Ensure that the battery On/Off switch is in the
On
position before closing the access door or the backup battery
will not work when it is most required.
9.8
Return to Factory Default Settings
If required, the system Administrator or a Honeywell Service Technician can return the TPPL Controller to its Factory
Default settings.
Passwords are not changed when resetting to Factory Default settings so this procedure cannot be used to restore
forgotten passwords to the default password.
9.8.1
To Reset the Touchpoint Plus to its Factory Default Settings
12)
Log in as Administrator.
13)
Touch
Maintenance>Service Mode>Reset to Default>Yes
.
14)
If required, recommission and reconfigure the Touchpoint Plus system (Ch. 6 Commissioning).
15)
Log out.
WARNING
Returning TPPL to its Factory Default settings will initialize all user settings including mA and mV Input
channel calibrations, Relay and mA Output settings etc.
Your TPPL system will become inoperative until it is reconfigured (see Ch. 6 Commissioning), and you should
put alternative safety arrangements in place until the system is returned to normal operation.