Commissioning
MAN0984_Iss 4_01/19
Touchpoint Plus
Pt. No. 3011M5001
63
Technical Handbook
6.13
Commission Input / Output Modules
1)
Login as Service or Administrator.
2)
Touch
Menu> Configuration>Module Control Panel
.
3)
Touch [Refresh] to check for additional modules (if an expansion unit is connected and switched on).
4)
Touch an I/O module (a blue block) and touch [Add]. Touch one of the listed I/O module types.
5)
Repeat for other installed I/O modules.
6)
To remove a module, select the Module on the screen and then touch [Remove]. To replace it, touch [Replace].
Note:
Sky blue blocks show uncommissioned or decommissioned modules.
6.14
Channel Configuration
Note:
Administrator or Service level access is required. Refer to Ch.7.4 Menu Items and Access Levels for details.
Note:
In order to disable calibration overdue warning, set the calibration interval to zero. (See Ch.6.14.2 Configuring a
Channel and Ch.6.14.3 Editing a Configured Channel).
The system will time out after fifteen minutes if not data is entered during channel configuration. Unsaved settings
will not be retained. The channel will be decommissioned. It may be necessary to return to the System Setup screen
and set the module to Normal state.
Note
: Refer to Ch.17 Configurable Parameter Reference Guide for the understanding of parameters.
6.14.1
Introduction
Individual channels can be configured in two ways either from the built in sensor catalogue (for Analogue Input
modules only), or by completing a full custom configuration.
When using the sensor catalogue, only the Analogue Channel number and tag must be manually entered and then
the rest of the configuration will be populated automatically when a detector is selected from the pre-defined list.
Note:
You can always use the sensor catalogue as a starting point and then amend it afterwards (see Ch.6.14.3
Editing a Configured Channel and Ch.17 Configurable Parameter Reference Guide).
To change any parameter, enter the new value and touch Apply to update the system. The system will then return the
value, which will be displayed on the screen, and the user must touch Update for the settings to take effect. This
requires the user to verify that the correct value has reached the system.