Function Parameter Index Reference
8/99
RS232 Communications Reference Manual
41
5.5 AI Function Block
Description
The AI label stands for Analog Input. This block is part of the Loops category. It looks like this
graphically on the Control Builder.
Dynamic Parameters:
Table 5-5
AI Dynamic Parameters
Parameter
Index
Type
Use
R/W
Description
status
0
REAL
C
R
Block Status (see section 5.2 for code list)
OUT
1
REAL
O
R
analog input value (eu)
FAIL
2
BOOL
O
R
Failed input indication
Static Configuration Parameters:
Table 5-6
AI Static Configuration Parameters
Parameter
Index
Type
Description
filt_time
2
REAL
filter time constant (seconds) {0-120} [default 0]
bias
3
REAL
bias (eu).{-99999 to 99999} [default 0]
failsafe
4
REAL
failsafe value (eu) [default 0]
range_hi
6
REAL
high range value [default 0]
range_lo
7
REAL
low range value [default 100]
Summary of Contents for RS-232
Page 12: ...Overview 2 RS232 Communications Reference Manual 8 99 ...
Page 24: ...Protocol Description 14 RS232 Communications Reference Manual 8 99 ...
Page 36: ...PC Communication Driver 26 RS232 Communications Reference Manual 8 99 ...
Page 143: ...Function Parameter Index Reference 8 99 RS232 Communications Reference Manual 133 ...
Page 150: ...Index 140 RS232 Communications Reference Manual 8 99 ...
Page 151: ......