Function Parameter Index Reference
46
RS232 Communications Reference Manual
8/99
5.10 AMB Function Block
Description
The AMB label stands for Auto/Manual Bias Function. This block is part of the Loops category. It looks
like this graphically on the Control Builder.
Dynamic Values:
Table 5-12 AMB Dynamic Values
Parameter
Index
Type
Use
R/W
Description
Status
0
REAL
C
R
block status
Bias
1
REAL
C
R
calculated bias (%)
Man_mode
2
BOOL
C
R/W
manual output mode request {OFF, ON}
Man_out
3
REAL
C
R/W
manual output value –5 to 105 (%)
Pv
4
REAL
C
R
Process Variable in % for monitoring
OUT
5
REAL
O
R
control output –5 to 105 (%)
MODE
6
REAL
O
R
actual mode encoded per note 3
ALl
7
BOOL
O
R
Alarm 1
AL2
8
BOOL
O
R
Alarm 2
PVI
9
REAL
I
R
Process Variable Input (%) (pv_lo <= PV <= pv_hi)
TRV
10
REAL
I
R
Output Track Value (%)
TRC
11
BOOL
I
R
Output Track Command {OFF, ON}
MDRQI
12
REAL
I
R
External Mode Request encoded per note 4