Function Parameter Index Reference
108
RS232 Communications Reference Manual
8/99
Dynamic Output Parameters:
Table 5-75 SPS Dynamic Output Parameters
Parameter
Index
Type
Use
R/W
Description
STA
40
REAL
O
R
program state {N/A, RESET, RUN, HOLD, GHOLD,
STOP}
SEG
41
REAL
O
R
current segment number
PGM
42
REAL
O
R
current program number
SP1
43
REAL
O
R
Setpoint #1 output ( EU)
SP2
44
REAL
O
R
Setpoint #2 output ( EU)
SP3
45
REAL
O
R
Setpoint #3 output ( EU)
SP4
46
REAL
O
R
Setpoint #4 output ( EU)
SP5
47
REAL
O
R
Setpoint #5 output ( EU)
SP6
48
REAL
O
R
Setpoint #6 output ( EU)
SP7
49
REAL
O
R
Setpoint #7 output ( EU)
SP8
50
REAL
O
R
Setpoint #8 output ( EU)
STMR
51
REAL
O
R
time remaining in current segment (minutes)
STME
52
REAL
O
R
time elapsed in current segment (minutes)
PTME
53
REAL
O
R
time elapsed in program (minutes).
STFL
54
REAL
O
R
current state flag
Dynamic Input Parameters:
Table 5-76 SPS Dynamic Input Parameters
Parameter
Index
Type
Use
R/W
Description
PV1
55
REAL
I
R
1
st
process variable (EU)
PV2
56
REAL
I
R
2
nd
process variable (EU)
PV3
57
REAL
I
R
3
rd
process variable (EU)
PV4
58
REAL
I
R
4
th
process variable (EU)
PV5
59
REAL
I
R
5
th
process variable (EU)
PV6
60
REAL
I
R
6
th
process variable (EU)
PV7
61
REAL
I
R
7
th
process variable (EU)
PV8
62
REAL
I
R
8
th
process variable (EU)
STRQ
63
REAL
I
R
Encoded state request from STSW block
NPGM
64
REAL
I
R
Program number (when SET is ON)
NSEG
65
REAL
I
R
Starting segment number (when SET is ON)
SET
66
BOOL
I
R
Pulse input to load PGM and SSEG numbers
Summary of Contents for RS-232
Page 12: ...Overview 2 RS232 Communications Reference Manual 8 99 ...
Page 24: ...Protocol Description 14 RS232 Communications Reference Manual 8 99 ...
Page 36: ...PC Communication Driver 26 RS232 Communications Reference Manual 8 99 ...
Page 143: ...Function Parameter Index Reference 8 99 RS232 Communications Reference Manual 133 ...
Page 150: ...Index 140 RS232 Communications Reference Manual 8 99 ...
Page 151: ......