Function Parameter Index Reference
124
RS232 Communications Reference Manual
8/99
use_rpm
33
BOOL
Use minutes (0) or repeats per minute (1) for integral constant
sp_rate_dn
34
REAL
Set point low rate of change limit, 0 (off) to 99999 (eu/min)
sp_rate_up
35
REAL
Set point high rate of change limit, 0 (off) to 99999 (eu/min)
RATIO
37
REAL
Gain value for Ratio PID (-20 to 20) (default 1) [ used when RA_BIAS
> 0]
LBIAS
38
REAL
Bias value for Ratio PID when RA_BIAS = LOC_BIAS](-99999 to
99999) (0)
devbar_hi
39
REAL
High scale value for deviation bar graph (0 to 99999) (default 100)
devbar_low
40
REAL
Low scale value for deviation bar graph [always = -devbar_hi]
deadband
43
REAL
adjustable gap between forward and reverse motor operation (.5 to 5%)
Summary of Contents for RS-232
Page 12: ...Overview 2 RS232 Communications Reference Manual 8 99 ...
Page 24: ...Protocol Description 14 RS232 Communications Reference Manual 8 99 ...
Page 36: ...PC Communication Driver 26 RS232 Communications Reference Manual 8 99 ...
Page 143: ...Function Parameter Index Reference 8 99 RS232 Communications Reference Manual 133 ...
Page 150: ...Index 140 RS232 Communications Reference Manual 8 99 ...
Page 151: ......