
96
SFP-5UD & SFP-10UD Series Manual—
P/N 52879:C2 1/24/2012
Programming
Master Programming Level
Ademco Contact ID Format - Secondary Central Station Phone Number
The information shown in Table 3.5 is automatically programmed for the Secondary Central Sta-
tion phone number Event Codes when Ademco Contact ID Format is selected. To disable event
reporting, select the desired Event Code to be disabled and press
0
or
Clear
and then
Enter
to dis-
able it. (
Enter
must be pressed to save the selection. Pressing
Escape
will not save the selection).
Event Description
Event Code Settings
Active
Secondary # Zone 1 - 10 Alarm
115
Secondary # Zone 1 - 10 Disabled
570
Secondary # Drill
604
Secondary # AC Fault
301
Secondary # Zone 1 - 10 Fault
380
Secondary # Zone 1 - 10 Dirty
380
Secondary # Earth Fault
310
Secondary # Low Battery Fault
302
Secondary # No Battery Fault
311
Secondary # Telco Primary Line Fault
351
Secondary # Telco Secondary Line Fault
352
Secondary # NAC #1 Fault
321
Secondary # NAC #2 Fault
322
Secondary # NAC #3 Fault
326
Secondary # NAC #4 Fault
327
Secondary # NAC #1 Disable
521
Secondary # NAC #2 Disable
522
Secondary # NAC #3 Disable
526
Secondary # NAC #4 Disable
527
Secondary # Charger Fault
300
Secondary # Comm Trouble Primary #
354
Secondary # Comm Trouble Secondary #
354
Secondary # Printer Fault
336
Secondary # ANN-BUS Fault
330
Secondary # Option Card Fault
333
Secondary # CS CALC Fault
304
Secondary # System Off Normal
308
Secondary # System Test Message
602
Secondary # System Abnormal Test Message
608
Secondary # Upload/Download Request
411
Secondary # Upload Successful
416
Secondary # Download Successful
412
Secondary # Upload/Download Failed
413
Secondary # Voice EVAC Fault
330
Secondary # Power Supply Sync fault
300
Table 3.5 Ademco Contact ID Secondary # Event Codes