SFP-5UD & SFP-10UD Series Manual—
P/N 52879:C2 1/24/2012
21
Digital Alarm Communicator/Transmitter
Product Description
1.4 Digital Alarm Communicator/Transmitter
Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1
for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs
are provided as well as a green
Kissoff
LED. The integral digital communicator provides the fol-
lowing functions:
•
Line Seizure: takes control of the phone lines disconnecting any premises phones
•
Off/On Hook: performs on and off-hook status to the phone lines
•
Listen for dial tone: 440 Hz tone typical in most networks
•
Dialing the Central Station(s) number: default is Touch-Tone
®
, programmable to rotary
•
For tone burst or touchtone type formats: discern proper
Ack
and
Kissoff
tone(s). The
frequency and time duration of the tone(s) varies with the transmission format. The control
panel will adjust accordingly.
•
Communicate in the following formats:
Ademco Contact ID
SIA-DCS-8
SIA-DCS-20
1.5 Components
Main Circuit Board
The main circuit board contains the system’s CPU, DACT and other primary components and wir-
ing interface connectors. Optional modules plug in and are mounted to the main circuit board.
Power Supply
One power supply is provided standard with each FACP, mounted to a chassis.
•
FLPS-3 for the SFP-5UD
•
FLPS-7 for the SFP-5UDC, SFP-10UD(C)/E
Cabinet
The backbox measures 16.65” (42.29 cm) x 19.0” (48.26 cm) x 5.207” (13.23 cm) and provides
space for two batteries (up to 18 Amp Hours). Also available are an optional dress panel (DP-
51050B (black) or DP-51050 (red)) which mounts inside the cabinet and trim-ring (TR-CE/B). The
Canadian version is supplied standard with a modified dress panel and one N-ANN-LED annuncia-
tor module.
Batteries
The cabinet provides space for two 18 Amp Hour batteries (larger batteries require use of a UL
listed battery box such as the NFS-LBB or BB-26). Batteries must be ordered separately.
1.6 Optional Modules and Accessories
N-CAC-5X Class A Converter Module
The N-CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits to
Style D (Class A) and Style Y (Class B) Notification Appliance Circuits to Style Z (Class A). The
module connects to J2 on the SFP-5UD and SFP-10UD main circuit board and to J7 on the SFP-
10UD. Note that two Class A Converter modules are required for the 10 zone panel.