18
SFP-5UD & SFP-10UD Series Manual—
P/N 52879:C2 1/24/2012
Product Description
Specifications
The following figure illustrates the maximum current that is possible for each major panel output
circuit and the total current available from the FACP with the FLPS-3 power supply. This applies
to the SFP-5UD and SFP-5UDE.
TB9
TB5
TB7
TB3
TB2
TB1
Figure 1.1 Current Availability with FACP and FLPS-3 Power Supply
po
we
rdi
st5
10
.w
mf
Refer to the battery calculations section for additional information.
Standby
1.0 amp max
per panel
Special Application
Nonresettable or
Resettable Power
Special Application
Resettable Power
NAC #1
NAC #2
NAC #3
NAC #4
0.5 amp max
per circuit
0.5 amp max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
Alarm
3.0 amps
max
per panel
Primary
ANN-BUS
Standby
1.0 amp max
per panel
0.5 amp max
per circuit
Remote
Synchronization
Output
0.040 amp max
per circuit
ANN-SEC
Option Card
0.5 amp max
per circuit