SFP-5UD & SFP-10UD Series Manual—
P/N 52879:C2 1/24/2012
Programming
Master Programming Level
Trouble Call Limit (Dialer Runaway Prevention)
The Call Limit option limits the number of DACT trouble calls to the Central Station, to a pro-
grammed amount between 0 and 99, for each unique trouble within a 24 hour period. All call limit
counters reset (clear) at each midnight. Separate limit counters keep track of each unique type of
trouble. Note that the number of phone line (communication) faults called to the Central Station
are not limited by this feature. No subsequent restoral message is sent to the Central Station(s) for
a particular trouble whose call limit has been reached. Local DACT annunciation will still track the
particular trouble and restoral.
Secondary # Zone 6 Dirty
FT6
FJ6
Secondary # Zone 7 Dirty
FT7
FJ7
Secondary # Zone 8 Dirty
FT8
FJ8
Secondary # Zone 9 Dirty
FT9
FJ9
Secondary # Zone 10 Dirty
FT10
FJ10
Secondary # Earth Fault
ET38
ER38
Secondary # Low Battery Fault
YT0
YR0
Secondary # No Battery Fault
YT0
YR0
Secondary # Telco Primary Line Fault
LT1
LR1
Secondary # Telco Secondary Line Fault
LT2
LR2
Secondary # NAC #1 Fault
ET32
ER32
Secondary # NAC #2 Fault
ET33
ER33
Secondary # NAC #3 Fault
ET34
ER34
Secondary # NAC #4 Fault
ET35
ER35
Secondary # NAC #1 Disable
ET101
ER101
Secondary # NAC #2 Disable
ET102
ER102
Secondary # NAC #3 Disable
ET103
ER103
Secondary # NAC #4 Disable
ET104
ER104
Secondary # Charger Fault
YP
YQ
Secondary # Comm Trouble Primary #
YC1
YK1
Secondary # Comm Trouble Secondary #
YC2
YK2
Secondary # Printer Fault
VT
VR
Secondary # ANN-Bus Fault
ET61
ER61
Secondary # Option Card Fault
ET
ER
Secondary # CS CALC Fault
YF
000
Secondary # System Off Normal
LB
LX
Secondary # System Test Message
RP
000
Secondary # System Abnormal Test Message
RP99
000
Secondary # Power Supply Sync Fault
OU
OV
Secondary # Upload/Download Request
RB
000
Secondary # Upload Successful
RS
000
Secondary # Download Successful
RS
000
Secondary # Upload/Download Failed
RU
000
Secondary # Voice EVAC Fault
ET
ER
Secondary # Power Supply Sync Fault
OU
OV
Table 3.7 SIA-DCS Secondary # Event Codes (Continued)
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=CALL LIMIT
Central Station Screen #2