Honeywell NOTIFIER SFP-10UD Series Manual Download Page 30

30

SFP-5UD & SFP-10UD Series Manual—

 P/N 52879:C2  1/24/2012

Installation

Input Circuits

2.3  Input Circuits

The SFP-5UD has five IDCs (Initiating Device Circuits) and the SFP-10UD has ten IDCs.  Each 
circuit is compatible with System Sensor’s i

3

 smoke detectors which generate a maintenance signal 

when the detector becomes dirty and a separate supervisory ‘freeze’ signal when ambient tempera-
ture falls below the detector rating of approximately 45

o

F.  The maximum loop resistance limit for 

each IDC is 100 ohms (700 ohms per zone for linear heat detection).  Do not use 2-wire smoke 
detectors on input zones used for linear heat detection.  The field wiring for each zone is supervised 
for opens, shorts and ground faults.  All conditions are visually and audibly annunciated.

Each circuit is configured for Style B (Class B) operation and will accept i

3

 smoke detectors, any 

normally-open contact devices as well as conventional 2-wire or 4-wire, 24 VDC smoke detectors. 
Refer to the Notifier Device Compatibility Document for a list of compatible devices.

Initiating Device Circuits can be converted to Style D (Class A) by installing the optional Class A 
Converter module.  Refer to “N-CAC-5X Class A Converter Module” on page 37.  

Figure 2.5  IDC Connections

Class B Initiating Device Circuits (supervised and power-limited) 4.7 K

, ½ watt resistor P/N:71252

UL listed compatible 
2-wire smoke detectors

manual pull stations

heat detectors

Dummy load all unused 
circuits - 4.7 K

, ½ watt 

resistor (P/N: 71245)

ms-

10

UDid

c.wmf

UL listed Power Supervision Relay

(refer to Device Compatibility Document for list of compatible relays)

Resettable 24 VDC 
4-wire smoke 
detector power 
(500 mA maximum)

UL listed compatible 4-wire smoke detector

Summary of Contents for NOTIFIER SFP-10UD Series

Page 1: ...C2 P N 52879 C2 ECN 12 056 Document 52879 1 24 2012 Rev Fire Alarm Control Panels SFP 5UD Series SFP 10UD Series Manual ...

Page 2: ... fire Smoke detectors cannot be expected to provide adequate warning of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predeter mined rate or reaches a predet...

Page 3: ...oards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifi cations verify that they will not interfere with battery trans former or printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may dam...

Page 4: ...opriate version for a specific application Documentation Feedback Your feedback helps us keep our documentation up to date and accurate If you have any comments or suggestions about our online Help or printed manuals you can email us Please include the following information Product name and version number if applicable Printed manual or online Help Topic Title for online Help Page number for print...

Page 5: ...ing Requirements 35 2 6 Digital Communicator 36 2 7 Installation of Optional Modules 37 2 7 1 N CAC 5X Class A Converter Module 37 Installation 37 Wiring NACs and IDCs for Class A 38 2 7 2 4XTM Option Module 39 4XTM Transmitter Module Installation 39 2 7 3 ANN SEC Option Card 40 2 8 ANN BUS Devices 41 Guidelines 41 2 8 1 ANN BUS Wiring 41 Calculating Wiring Distance for ANN BUS Modules 41 Wiring C...

Page 6: ...hibited 74 3 5 3 Relays 74 3 5 4 System Setup 75 Timers 76 Banner 78 Time Date 79 Trouble Reminder 81 Canadian Option 81 Charger Disable 81 3 5 5 Option Modules 81 ANN BUS 82 ANN RLY Options Screen 87 ANN AUDIO Options Screen 87 ANN SEC Enable 88 Onboard DACT 89 3 5 6 History 102 View Events 102 Erase History 103 3 5 7 Walktest 103 3 5 8 Clear Program 104 3 5 9 Password Change 104 3 6 Maintenance ...

Page 7: ...9 7 History 124 4 19 8 Print 124 4 19 9 ANN BUS 125 4 19 10 Central Station 126 4 19 11 Phone Line 126 4 19 12 Service Terminal 127 Section 5 Central Station Communications 129 5 1 Transmittal Priorities 130 Section 6 Local Remote Site Upload Download 132 6 1 Remote Download 132 6 2 Transferring a Program 133 6 2 1 Security Features 134 Section 7 Power Supply Calculations 135 7 1 Overview 135 7 2 ...

Page 8: ...dix C FACP with Keltron 152 Appendix D Wire Requirements 153 D 1 SFP 5UD E NAC Wiring 154 D 2 SFP 5UDC SFP 10UD C E NAC Wiring 154 Appendix E Default Programming 155 Appendix F Canadian Application 156 F 1 N ANN LED Annunciator Installation for Canadian Applications 156 Index 158 ...

Page 9: ...eneral Purpose Signaling Devices and Systems CAN ULC S524 01 Standard for Installation of Fire Alarm Systems CAN ULC S559 Standard for Equipment for Fire Signal Receiving Centers and Systems This Class A digital apparatus complies with Canadian ICES 003 Cet appareil numérique de la classe A est conforme à la norme NMB 003 du Canada Other Canadian Electrical Code Part I NEC Article 250 Grounding NE...

Page 10: ... card connector USB port for local programming using a personal computer and PK 5X Utility DACT Phone Line Jacks Nonpower Limited Battery see note 3 24 VDC supervised nonpower limited Basic System Connections 5 Zone Panel Power Supply Connector For more specific UL wiring information refer to page 35 Important Removing Ground Fault Disable Jumper JP43 voids UL NFPA Style Class indentifications for...

Page 11: ...24 VDC supervised nonpower limited Basic System Connections 10 Zone Panel Power Supply Connector For more specific UL wiring information refer to page 35 Important Removing Ground Fault Disable Jumper JP43 voids UL NFPA Style Class indentifications for circuits Remove jumper JP43 only with the approval of the local AHJ Authority Having Jurisdiction Special Application DC Power Outputs 24 VDC Nonsu...

Page 12: ...NE 6 ALM TBL SUP 6 NAC 1 Fault Battery Fault ZONE 2 ALM TBL SUP 2 ZONE 7 ALM TBL SUP 7 NAC2 Fault Charger Fault ZONE 3 ALM TBL SUP 3 ZONE 8 ALM TBL SUP 8 FIRE ALARM ANNUNCIATOR NAC 4 Fault ZONE 5 ALM TBL SUP 5 ALM TBL SUP NAC 3 Fault Disabled ZONE 4 ALM TBL SUP 4 ZONE 9 ALM TBL SUP 9 FROM AP PHONE PSTN TO A P OUT NC OU T NO INPUT TAMPER GND 12 24V P4 CN2 P 5 P6 P7 P8 P9 P10 P11 P12 CHG 120 Charger...

Page 13: ...ree programmable Form C relays factory programmed for Alarm Trouble and Supervisory and 24 VDC special application reset table and nonresettable power outputs The FACP supervises all wiring AC voltage battery level and telephone line integrity Available accessories include local and remote upload download soft ware remote annunciators and reverse polarity city box transmitter The integral DACT tra...

Page 14: ... LED Annunciator Module 80 character LCD display backlit Real time clock calendar with daylight savings time control History log with 256 event storage Control Buttons ACK Acknowledge FACP Version Description SFP 5UD Five Zone Panel 120 VAC with FLPS 3 power supply providing 3 0 amps total 24 VDC output current SFP 5UDC Five Zone Panel 120 VAC with FLPS 7 power supply providing 7 0 amps total 24 V...

Page 15: ...ional 4XTM Transmitter Module Optional ANN SEC card for a secondary ANN BUS 1 2 Specifications AC Power SFP 5UD FLPS 3 Power Supply 120 VAC 60 HZ 1 00 amps SFP 5UDC FLPS 7 Power Supply 120 VAC 60 HZ 3 90 amps SFP 10UD C FLPS 7 Power Supply 120 VAC 60 HZ 3 90 amps SFP 5UDE FLPS 3 Power Supply 240 VAC 50 HZ 0 54 amps SFP 10UDE FLPS 7 Power Supply 240 VAC 50 HZ 2 20 amps Wire size minimum 14 AWG 2 0 ...

Page 16: ...otifier Device Compatibility Document for compatible listed devices Form C Relays Programmable TB8 Relay 1 factory default programmed as Alarm Relay Relay 2 factory default programmed as fail safe Trouble Relay Relay 3 factory default programmed as Supervisory Relay Relay Contact Ratings 2 amps 30 VDC resistive 0 5 amps 30 VAC resistive Special Application Resettable Power TB9 Operating Voltage No...

Page 17: ...ication power Maximum current is 40 mA End of Line Resistor 4 7K Supervised and power limited circuit Auxiliary Trouble Input J6 The Auxiliary Trouble Input is an open collector circuit which can be used to monitor an external device for trouble conditions It can be connected to the trouble bus of a peripheral such as a power supply which is compatible with open collector circuits All connections ...

Page 18: ... Power Supply powerdist510 wmf Refer to the battery calculations section for additional information Standby 1 0 amp max per panel Special Application Nonresettable or Resettable Power Special Application Resettable Power NAC 1 NAC 2 NAC 3 NAC 4 0 5 amp max per circuit 0 5 amp max per circuit 2 5 amps max per circuit 2 5 amps max per circuit 2 5 amps max per circuit 2 5 amps max per circuit Alarm 3...

Page 19: ...ent Availability with FACP and FLPS 7 Power Supply powerdistmrp wmf Refer to the battery calculations section for additional information Standby 1 0 amp max per panel Special Application Nonresettable or Resettable Power Special Application Resettable Power NAC 1 NAC 2 NAC 3 NAC 4 0 5 amp max per circuit 0 5 amp max per circuit 3 0 amps max per circuit 3 0 amps max per circuit 3 0 amps max per cir...

Page 20: ... Reset lamp test Service program keys Keys labeled 1 to 9 key key 0 recall key 1st Event key Clear key Escape key Mode key Four cursor keys up down left and right Enter key LED Indicators LEDs are provided to annunciate the following conditions Fire Alarm red LED Supervisory yellow LED AC Power green LED System Trouble yellow LED Alarm Silence yellow LED Primary Phone Line Active on circuit board ...

Page 21: ...ns the system s CPU DACT and other primary components and wir ing interface connectors Optional modules plug in and are mounted to the main circuit board Power Supply One power supply is provided standard with each FACP mounted to a chassis FLPS 3 for the SFP 5UD FLPS 7 for the SFP 5UDC SFP 10UD C E Cabinet The backbox measures 16 65 42 29 cm x 19 0 48 26 cm x 5 207 13 23 cm and provides space for...

Page 22: ...ied graphic annunciator ANN SEC Secondary ANN BUS Module The ANN SEC module provides another ANN BUS port for more wiring flexibility and for Cana dian applications requiring remote annunciation DP 51050 B Dress Panel A dress panel DP 51050B black or DP 51050 red is available as an option The dress panel restricts access to the system wiring while allowing access to the membrane switch panel The C...

Page 23: ... Requirements and Warnings 1 7 1 Telephone Circuitry Ringer Equivalence Number REN 0 0B AC Impedance 10 0 Mega Ohm Complies with FCC Part 68 Mates with RJ31X Male Connector Supervision Threshold loss of phone line voltage for 2 minutes The REN is used to determine the quantity of devices which may be connected to the telephone line Excessive RENs on the telephone line may result in the devices not...

Page 24: ...required Do not connect both telephone interfaces to the same tele phone line The control panel must be connected to the public switched telephone network upstream as first device of any private telephone system at the protected premises A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the applicable FCC Part 68 rules and requirements ado...

Page 25: ...to a telephone interface the termi nation of an interface may consist of any combination of devices subject only to the requirement that the sum of the REN of all devices does not exceed 5 DOC Compliance This digital apparatus does not exceed the Class A limits for radio noise emis sions from digital apparatus set out in the Radio Interference Regulations of the Canadian Depart ment of Communicati...

Page 26: ...ate backbox mounting the chassis with main circuit board and transformer can be easily removed Loosen the two 3 8 nuts securing the top flanges of the chassis then slide the chassis up to free it from the lower tabs Place the chassis assembly in a protective antistatic bag in a safe location until it can be reinstalled in the backbox Mark and predrill hole in the wall for the center top keyhole mo...

Page 27: ...9050UDencl wmf Figure 2 2 Cabinet Dimensions Hinge Slot for optional Dress Panel Semi Flush mounting hole Mounting slots for optional Trim Ring Hinge Slot for optional Dress Panel Semi Flush Mounting Do not recess box more than 3 875 into wall to avoid covering venting holes on top of box ...

Page 28: ...ain power supply As per the National Electrical Code use 14 AWG 2 00 mm2 1 6 mm O D or heavier gauge wire with 600V insulation No other equipment WARNING RISK OF ELECTRICAL SHOCK AND OR EQUIPMENT DAMAGE SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL DISCONNECT ALL SOURCES OF POWER BEFORE SERVICING THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING AND OR INSERTING CAR...

Page 29: ...ve polarity when connecting the battery Connect the battery cable to J12 on the main circuit board using the plug in connector and cable provided The battery charger is current limited and capable of charging sealed lead acid batteries The charger shuts off when the system is in alarm WARNING SULFURIC ACID BATTERIES CONTAINS SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN AND EYES AND CAN D...

Page 30: ...ibly annunciated Each circuit is configured for Style B Class B operation and will accept i3 smoke detectors any normally open contact devices as well as conventional 2 wire or 4 wire 24 VDC smoke detectors Refer to the Notifier Device Compatibility Document for a list of compatible devices Initiating Device Circuits can be converted to Style D Class A by installing the optional Class A Converter ...

Page 31: ... 2 6 Program the FACP Initiating Device Circuit as a Combination circuit as described in Input Zones on page 62 Note that since a Waterflow Supervisory Switch is included in a Combination circuit the waterflow delay must be taken into consideration Refer to Waterflow Delay on page 77 Waterflow Alarm Switch activation causes the panel to latch into alarm until the alarm condition is cleared and the...

Page 32: ...s on page 135 Each circuit is supervised power limited and provides special application power Refer to the Notifier Device Compatibility Document for a listing of compatible notification appliances The NACs can be converted to Style Z Class A by installing the optional Class A Converter mod ule Refer to N CAC 5X Class A Converter Module on page 37 Figure 2 7 NAC Connections Class B Notification Ap...

Page 33: ...lay connections must be power limited Figure 2 8 Special Application Auxiliary Power Special Application 4 Wire Smoke Detector Power 500 mA 24 VDC filtered resettable power for 4 wire smoke detectors can be obtained from these terminals power limited Special Application Resettable or Nonresettable Power 500 mA 24 VDC filtered resettable or nonresettable power can be obtained from these terminals p...

Page 34: ...FP 5UD this can be accomplished by connecting the Remote Synchro nization Output from TB2 of the FACP to a compatible sync input of a power supply such as the FCPS 24S6 8 The 24 VDC 40 mA signal from TB2 follows that is mimics the signal on NAC 1 Out 1 This allows the devices connected to the power supply to be synchronized with the devices connected to Out 1 on the FACP For the SFP 5UDC SFP 10UD ...

Page 35: ...lim ited circuit wiring Furthermore all power limited and nonpower limited circuit wiring must enter and exit the cabinet through different knockouts and or conduits A typical wiring diagram is illus trated below J13 Figure 2 11 Typical UL Power limited Wiring Requirements Power limited Circuits Class 2 Power limited Circuits Class 2 Nonpower limited Circuit AC Power N CAC 5X 10udULwire2 wmf 4XTM ...

Page 36: ... shown below Figure 2 12 DACT Installation Customer Premises Equipment and Wiring Telephone Line FACP with DACT Network Service Provider s Facilities Network Demarcation Point RJ31X Jack Unused RJ 11 Jack Unused J 11 Jack Telephone Telephone Telephone Answering System Fax Machine Computer 9050ACTAdact wmf 1 2 3 4 5 6 7 7 8 1 2 3 4 5 6 8 J8 J9 Figure 2 13 Wiring Phone Jacks 10UDJACK2 wmf RJ31X Jack...

Page 37: ...5X with J2 on the FACP main circuit board and press the module securely into place Make certain the pins are properly aligned to prevent bending or breaking of any con nector pins Secure the N CAC 5X to the standoffs with the screws that were just removed To install the second N CAC 5X on J7 of the SFP 10UD remove the main circuit board mounting screw referenced in the following illustration and r...

Page 38: ...urn for the negative side of a device To configure any of the zones for Class B when the N CAC 5X is installed simply wire to the B and B input on the FACP terminal s and install the End of Line Resistor after the last device on the circuit Do not wire to the corresponding A and A terminals on the N CAC 5X module Figure 2 15 Wiring NACs and IDCs for Class A Operation N CAC 5X Class A Converter Mod...

Page 39: ...in circuit board with the supplied screws 6 For proper 4XTM operation the output relays must be programmed for the factory default settings Alarm Relay 1 Trouble Relay 2 and Supervisory Relay 3 7 When the installation has been completed connect the wiring to the modules as indicated in the following sections 8 Test system for proper operation 4XTM Transmitter Module Installation The 4XTM provides ...

Page 40: ...ED will illuminate after the module is installed in the FACP In addition the System Trouble LED will turn on to indicate the Disconnect condition 2 7 3 ANN SEC Option Card The ANN SEC option card allows for a secondary ANN BUS Install the ANN SEC as follows 1 Remove the chassis mounting screw to the right of TB3 and replace it with the supplied 0 5 x 4 40 male female standoff 2 Install the header ...

Page 41: ...e N ANN I O LED Driver Module N ANN LED Annunciator Module N ANN RLY Relay Module can be mounted in the FACP chassis When operating two ANN BUS circuits only one ANN S PG Printer module can be used in the system The panel is capable of operating a primary ANN BUS TB3 and a secondary ANN BUS TB1 on ANN SEC card simultaneously 2 8 1 ANN BUS Wiring This section contains information on calculating ANN...

Page 42: ...et 1 800 m regardless of gauge used The formula used to generate this chart is shown in the note below The following formulas were used to generate the wire distance chart Model Number Worst Case Current Draw1 1 Total worst case current draw on a single ANN BUS cannot exceed 0 5 amp N ANN 80 C LCD Annunciator Indicator 0 040 amps N ANN S PG Serial Parallel Printer Interface Module 0 040 amps N ANN...

Page 43: ...Driver Module The total worst case current is calculated as follows Using this value and referring to the Wiring Distance Table 2 1 on page 42 it can be found that the available options are 463 feet maximum using 22 Gauge wire 1 172 feet maximum using 18 Gauge wire 1 866 feet maximum using 16 Gauge wire 2 953 feet maximum using 14 Gauge wire Wire Gauge Ohms per 1 000 feet Rpu 22 16 2 18 6 4 16 4 0...

Page 44: ...CP s Secondary ANN BUS via the ANN SEC option card and ANN BUS devices Figure 2 19 FACP wiring to ANN BUS Device on Primary ANN BUS FACP N ANN 80 ANN BUS and power wiring are supervised and power limited TB3 Primary ANN BUS ann80to5x wmf TB1 J1 A B ANN SEC Figure 2 20 FACP wiring to ANN BUS Device on Secondary ANN BUS via ANN SEC FACP N ANN 80 ANN BUS and power wiring are supervised and power limi...

Page 45: ...of 8 devices can be connected to the FACP ANN BUS communication circuit Device addresses do not need to be sequential and can be set to any number between 01 and 08 Note that 00 is not a valid address The following table shows the DIP switch setting for each address Figure 2 21 Powering ANN BUS Devices from FCPS 24S6 8 N ANN 80 SFP 5UD SFP 10UD FCPS 24S6 8 24 VDC 24 VDC ANN BUS Cut Ground Fault De...

Page 46: ...tered and nonresettable Normal Standby no activity 37 0 mA Trouble 39 0 mA Alarm 40 0 mA AC Fail not backlit 15 0 mA For use indoors in a dry location Installation Ensure that all power AC and DC has been removed from the FACP before installing the annunci ator Opening Closing Annunciator The following procedure details the steps used to open the annunciator in order to access the termi nal block ...

Page 47: ...cover cannot be reattached or removed after the annunciator has been mounted Wiring N ANN 80 to FACP The following steps can be used as a guide to wire the annunciator Make certain all power has been removed from the FACP prior to annunciator installation 1 Route wires from hole in backplate through wiring channel and then to N ANN 80 terminal block TB1 2 Remove appropriate amount of wire insulati...

Page 48: ...added to the system via FACP programming Refer to the programming section titled ANN BUS on page 82 in this manual for detailed programming information Select the LCD option for programming 2 8 4 N ANN S PG Serial Parallel Printer Interface Installation The N ANN S PG Serial Parallel Printer Interface module allows the ancillary connection of a serial or parallel printer to the FACP for a real tim...

Page 49: ...umns of data on standard 9 x 11 tractor feed paper This section con tains information on connecting a printer to the control panel and setting the printer options Connecting PRN 6 Printer Remote printers require a primary AC power source If required for the fire alarm system configu ration for example a Proprietary Fire Alarm System a remote printer requires a secondary power source battery backup...

Page 50: ...le Option Setting Option Setting Font HS Draft CPI 10CPI LPI 6 LPI Skip 0 5 ESC Character ESC Emulate Epson FX 850 Bidirectional Copy ON I O CG TAB Graphic Buffer 40K Country E US ASCII Serial Auto CR OFF Baud 9600 or 2400 Color Option Not Installed Format 7 Bit Even 1 Stop Formien Protocol XON XOFF Lines 6LPI 60 Character Set Standard Standard Exec 10 5 SI Zero On Auto LF On PAPER BIN 1 12 72 BIN...

Page 51: ...tion titled ANN BUS on page 82 for programming information N ANN I O Board Layout Figure 2 24 illustrates the N ANN I O board showing locations of screw terminals for connection to the FACP pin connectors for connecting LEDs and the DIP switch for selecting the ANN BUS ID number Specifications Max ANN BUS Voltage 28 VDC Max Current Alarm 200 mA Standby 35 mA Each LED 10 mA Operating Temperature 32...

Page 52: ...nnectors on the N ANN I O module for connecting LEDs Each set of 10 LEDs get their power from Pin 11 of the corresponding connector Internal resistors are sized so that there is approximately 10 mA of current for each LED No series resistors are required LED outputs are mapped to output circuits Refer to the section titled ANN I O LED Zone Assign ments on page 85 of this manual Figure 2 25 N ANN I...

Page 53: ...l system faults and input zones when used with a compatible FACP The N ANN LED module provides alarm red trouble yellow and supervisory yellow indication for up to ten input zones Canadian Applications The N ANN LED is supplied standard with the MS 5UD 7C and MS 10UD 7C models It is mounted to the dress panel included with these models Specifications Max ANN BUS Voltage 24 VDC Max Current Alarm 68...

Page 54: ...P 2 8 7 N ANN RLY Relay Module The N ANN RLY relay module provides 10 programmable Form C relays when used with a com patible FACP Specifications Operating Voltage 24 VDC Max Current Alarm 75 mA Standby 15 mA Relay Contact Ratings 2 amps 30 VDC resistive 0 5 amps 30 VAC resistive Operating Temperature 32o F to 120o F 0o C to 49o C For indoor use in a dry location only Figure 2 27 N ANN LED Board L...

Page 55: ... ROME Series Installation Document 53530 for mount ing in the separate backbox mounting holes mounting hooks through mounting slots grounding wire N ANN RLY ANN MBRLY mounting bracket mounting holes mounting holes FACP Backbox Installation using ANN MBRLY mounting bracket FACP Chassis Installation mounting holes mounting holes N ANN RLY on ANN MBRLY mounting bracket ROME Series Installation using ...

Page 56: ...50ZS T Series Audio Panel manual document 52290 The NFV 25 50ZS T Series audio panel connects to the FACP via the ANN BUS communication circuit The five input zones on the SFP 5UD correspond to the first five NFV 25 50ZS T Series audio zones and the ten input zones on the SFP 10UD correspond to the first ten NFV 25 50ZS T Series audio zones The programmer can select which of the five audio message...

Page 57: ...l Call Zone If this zone goes into alarm all NFV 25 50ZS T Series audio zones will activate refer to ANN AUDIO Options Screen on page 87 A fault at the NFV 25 50ZS T Series panel will cause the FACP to indicate a System Trouble and the display will indicate a Voice Evac Fault The only connection between the SFP 5UD 10UD and the NFV 25 50ZS T audio panel is a pair of communication wires connected b...

Page 58: ...corporates field programmable software In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems UL 864 certain programming features or options must be limited to specific values or not used at all as indicated below Program feature or option Permitted in UL 864 Y N Possible settings Settings permitted in UL 864 Trouble Call L...

Page 59: ...e keypad ESC Escape key until the display reads System All Normal Ten minutes of inactivity will also cause the panel to exit Pro gramming Mode Note that the data which is entered during Programming mode is not saved until the programmer exits this mode by repeatedly pressing the ESC key If the Reset key is pressed or power is lost before exiting Programming mode all data just entered will be lost...

Page 60: ...e that subscreens may also have multiple options which require viewing more than one screen The same process as detailed in the previous paragraphs is followed to view all option choices 3 4 Programming and Passwords There are two factory set programming passwords which will access the Programming screens as indicated in the following examples From either of the screens access to specific system a...

Page 61: ... panel will enter user Program ming mode In this mode the piezo sounder remains off the trouble relay is activated and the sys tem Trouble LED flashes until Programming mode is exited The following display will appear The down arrow which appears in the display indicates that additional programming choices can be viewed by pressing the down arrow key on the keypad If a down and up arrow appear in ...

Page 62: ... Input Zones 4 through 10 in the SFP 10UD To program a specific zone press the number key corresponding to the desired zone while viewing one of the Input Zone screens To program Input Zone 1 press the 1 key while viewing Input Zone Screen 1 The following screens will be displayed To change the programming for the displayed zone press the keyboard down arrow key to view the Edit Zone screens PROGR...

Page 63: ...LCD will display the zone which has been disabled and FACP will turn on the Trouble LED Type To select the type of zone being programmed press the 2 key while viewing the Edit Input Zone Screen 2 This will cause the control panel to display the following Zone Type Screen INPUT ZONE 1 1 ENABLED YES 2 TYPE PULL STATION 3 VERIFICATION NO Edit Input Zone Screen 2 INPUT ZONE 1 1 PAS PRE SIG DELAY NO DE...

Page 64: ...R nonlatching uses waterflow delay 2 Wire Detector Fire Alarm Normally Open Contact Fire Alarm Fire Fire Alarm Tamper Supervisory Supervisory Supervisory latching Supervisory AutoResettable Supervisory nonlatching Medic Alert Supervisory latching Hazard Alert Supervisory latching Tornado Alert Supervisory latching Proc Mon Piezo Procmon AR Piezo nonlatching AC Loss Mon Trouble Ack Switch Acts like...

Page 65: ...up to three minutes while allowing for visual verification by a person Note that the alarm relay and communicator will respond to the initial alarm immediately To enable the Pre signal feature press 2 while viewing PAS Pre Signal Screen Refer to Presignal on page 118 PAS The PAS Positive Alarm Sequence option will program the zone to delay panel activation includ ing alarm relay and communicator f...

Page 66: ...o zone when this input goes active If MESSAGE 1 through 5 is the programmed option the selected message will play when the FACP is connected to an NFV 25 50ZST Audio Panel via the ANN BUS and the corresponding FACP input zone goes into alarm Adjective Noun The Adjective Noun selection allows the programmer to enter specific descriptors about the detec tor currently being programmed Pressing 1 whil...

Page 67: ...g to the adjective that is to be used as a descriptor for the location of the detector currently being programmed When an adjective has been selected it will appear at the top of the display as indicated by the asterisks 1 NORTH 2 SOUTH 3 EAST Adjective Screen 1 1 WEST 2 FRONT 3 CENTER Adjective Screen 3 1 REAR 2 UPPER 3 LOWER Adjective Screen 5 1 MAIN 2 FIRST 3 2ND Adjective Screen 7 1 3RD 2 4TH ...

Page 68: ...on of the detec tor currently being programmed When a noun has been selected it will appear at the top of the display as indicated by the asterisks 1 STANDARD ADJECTIVE 2 STANDARD NOUN 3 CUSTOM ADJECTIVE 4 CUSTOM NOUN Adjective Noun Screen 1 BASEMENT 2 BOILER RM 3 CLASSROOM Noun Screen 1 1 CLOSET 2 CORRIDOR 3 ELECTRIC RM Noun Screen 3 1 ELEVATOR 2 ENTRANCE 3 FLOOR Noun Screen 5 1 GARAGE 2 HALLWAY ...

Page 69: ...ve been entered press the Enter key to store the information The display will return to the Edit Input Zone Screen 4 dis playing the new information at the bottom of the screen Recall Increment Function In addition the user may use the Recall Increment function at any time when the cursor is on the first letter of the Description Adjective or Noun field as follows If the zero key is pressed a 0 is...

Page 70: ...NAC 4 To program an NAC circuit press the number corresponding to the NAC to be programmed The following screens will be displayed for each selection Enabled Pressing 1 while viewing NAC Screen 1 will cause the display to change to Enabled No This will prevent the selected main circuit board NAC from activating its devices Each press of the 1 key will cause the display to toggle between Enabled Ye...

Page 71: ...nds on and 5 seconds off Temporal second on second off second on second off second on 1 second off Two Stage 3 Minutes or 5 Minutes refer to Two Stage Operation on page 72 for a description of this feature Synchronized output for System Sensor Wheelock Gentex Faraday or Amseco Refer to Synchronized NAC Operation on page 72 for additional information Selection of one of the above options will cause...

Page 72: ...ed in step 1 NACs already in 2nd stage activation will not be affected Synchronized NAC Operation Synchronization is a panel feature that controls the activation of notification appliances in such a way that all devices will turn on and off at exactly the same time This is particularly critical when activating strobes which must be synchronized to avoid random activation and a potential hazard or ...

Page 73: ... zation Important When a Notification Appliance Circuit with a mix of audible and visual devices is pro grammed for Sync Mute only the audible devices will be turned off if the Silence key is pressed or if the Autosilence feature is enabled The visual devices strobes etc will continue to operate Auto Silence The Auto Silence feature when enabled automatically silences all main circuit board silenc...

Page 74: ...en 2 will cause a screen to be displayed with the options 1 No Silence Inhibit and 2 1 Min Silence Inhibit Pressing 1 will disable the Silence Inhibit feature while pressing 2 will enable a 1 minute Silence Inhibit for the selected Output 3 5 3 Relays Pressing 3 while viewing Programming Screen 1 will allow the programmer to configure the three main circuit board Form C relays The following screen...

Page 75: ...P after the control panel has been silenced The control panel piezo sounder will pulse once every 15 seconds during an alarm and every two minutes during a trouble condition after the Alarm Silence or Acknowledge key is pressed The piezo will continue to sound at these rates until the alarm or trouble condition is cleared If the Trouble Reminder feature is not enabled and a trouble condition is no...

Page 76: ... such as 005 for five seconds Upon entering the third digit the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indi cate the new delay time Pre signal Delay The factory default setting for Pre signal delay is 000 for no delay To select a Pre signal delay of 001 to 180 seconds for all devices programmed for Pre signal press 2 while v...

Page 77: ...nter a delay time consisting of two digits such as 25 for twenty five seconds Upon entering the second digit the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indicate the new delay time AC Loss Delay The reporting of a loss of AC power to a central station can be delayed by programming the length of the desired delay Press 1 while...

Page 78: ...play A maximum of 20 characters including spaces can be entered into the screen After entering up to 20 characters in the screen press Enter to store the entry To quickly clear the current banner press the CLR key To enter alphanumeric characters from the keypad repeatedly press the appropriate key until the desired character is displayed in the first position For example to enter the letter B pre...

Page 79: ...er 1 for AM or 2 for PM The display will then return to the Time Date Screen which will show the new time entry If an error is made while entering a digit press the CLR key to delete the entire entry and beginning again Date To change the date press 2 while viewing the Time Date Screen The following screen will be dis played A flashing cursor is located toward the top left of the display Below the...

Page 80: ...een 1 will display two sub screens which allow the programmer to select the week of the month that daylight savings time will begin In the first sub screen pressing 1 will select the first week 2 will select the second week and 3 will select the third week while in the second sub screen pressing 1 will select the fourth week and 2 will select the last week of the selected month Pressing 1 while vi...

Page 81: ...dary ANN BUS The Canadian Options configures the FACP with the following as required by Canada The following zone type codes are not available non latching supervisory non latching drill process monitor latching or non latching hazard tornado medical alert combo autoresettable The auto silence feature can be enabled or disabled If this feature is enabled the alarm signals will be turned off after ...

Page 82: ...ble the ANN BUS press 1 while viewing ANN BUS screen 1 so that the display reads ANN BUS Enabled Yes Each press of the 1 key will cause the display to toggle between ANN BUS Enabled Yes and ANN BUS Enabled No BUS Modules If an ANN BUS module is installed press 2 while viewing ANN BUS screen 1 to select ANN BUS addresses for the module s The following screen will be displayed ANN BUS 1 BUS ENABLED ...

Page 83: ...th the selected address This will enable the module Auto Configure The ANN BUS Auto Configure features allows the programmer to quickly bring all installed ANN BUS modules online The software will search for all ANN BUS modules and automatically program the device type and address into the system Pressing 3 while viewing ANN BUS Screen 1 will begin the Auto Configure process and cause the followin...

Page 84: ...le viewing Print Options screen 1 The resultant screen allows the programmer to program the Offline Timer for a delay of between 0 and 255 seconds before loss of printer supervision is reported as a trouble If the Serial Port option is selected the Printer Supv and Offline Timer options will not be available The Baud Rate Data Bits Parity and Stop Bits options are only available when the Serial Po...

Page 85: ...harger Fault 9 Disable 10 Maintenance 11 Zone 1 Alarm 12 Zone 2 Alarm 13 Zone 3 Alarm 14 Zone 4 Alarm 15 Zone 5 Alarm 16 Zone 6 Alarm 17 Zone 7 Alarm 18 Zone 8 Alarm 19 Zone 9 Alarm 20 Zone 10 Alarm 21 Zone 1 Trouble 22 Zone 2 Trouble 23 Zone 3 Trouble 24 Zone 4 Trouble 25 Zone 5 Trouble 26 Zone 6 Trouble 27 Zone 7 Trouble 28 Zone 8 Trouble 29 Zone 9 Trouble 30 Zone 10 Trouble 31 Zone 1 Supervisor...

Page 86: ...Ack Btn Enable No Ack Step button never functions The Silence Button Enable SIL BTN ENABLE option allows the programmer to select whether the Silence button on any installed N ANN 80 annunciator will function normally or always be ignored Pressing 1 while viewing the ANN 80 Options Screen 2 causes the display to toggle between Sil Btn Enable Yes Silence button functions normally and Sil Btn Enable...

Page 87: ...ponding to the relay to be programmed Following is a list of the available programming options for each relay General Alarm General Trouble General Supervisory AC Loss Waterflow Delay Input Zone 1 Input Zone 2 Input Zone 3 Input Zone 4 Input Zone 5 Input Zone 6 Input Zone 7 Input Zone 8 Input Zone 9 Input Zone 10 Silenceable Alarm Not Assigned ANN AUDIO Options Screen Pressing 1 for ANN AUDIO Opti...

Page 88: ...f any modules are connected to the ANN SEC option card at J13 To enable the Secondary ANN BUS press 2 while viewing ANN BUS Screen 3 so that the display reads ANN SEC ENABLE YES Each press of the 2 key will cause the display to toggle between ANN SEC ENABLE YES and ANN SEC ENABLE NO The factory default setting is ANN SEC ENABLE NO ANN AUDIO ALL CALL 1 NO ALL CALL ZONE 2 INPUT ZONE 1 3 INPUT ZONE 2...

Page 89: ...lect Rotary dialing with a make break ratio of 60 40 Secondary Phone Press 2 while viewing Onboard DACT Screen 1 to program the type of secondary phone line being connected to the DACT The following screen will be displayed OPTION MODULES 1 ANN BUS 2 ON BOARD DACT Option Module Screen ANN BUS 1 ANN AUDIO OPTIONS 2 ANN SEC ENABLE NO ANN BUS Screen 3 ON BOARD DACT 1 PRIM PHONE TCH TNE 2 SCND PHONE T...

Page 90: ...and or secondary central station phone numbers as a backup Press 2 while viewing Central Station Screen 1 to display the follow ing screen Press 1 to have all reports transmitted to the central station secondary phone number as a backup only if the primary phone line fails 2 to transmit all reports to both the primary and secondary phone numbers all of the time or 3 to send reports to the first av...

Page 91: ...nce every 6 8 12 or 24 hours Select the desired Test Time Interval by pressing the corresponding digit in the screens shown above CENTRAL STATION 1 TEST TIME INT 24 2 ACCOUNT CODE 0000 3 24HR T TIME 0000 Primary Secondary Screen 1 CENTRAL STATION 1 PHONE NUMBER Primary Secondary Screen 2 CENTRAL STATION 1 COMM FORMAT ADEMCO CONTACT ID 2 EVENT CODES Primary Secondary Screen 3 CENTRAL STATION 1 TEST...

Page 92: ...nter a four digit number representing the test time using military time 0000 midnight and 2359 11 59PM Phone Number Pressing 1 while viewing Primary Secondary Screen 2 will cause the following screen to be dis played The Phone Number screen is used to enter the Central Station phone number that the DACT will be contacting A maximum of 20 characters can be entered with valid entries being 0 9 and A...

Page 93: ... Comm Format screen The following table describes each format Event Codes Pressing 2 while viewing Primary Secondary Screen 3 will cause the following screen to be dis played Pressing the down arrow key allows viewing of all Events associated with the selected Communi cation Format Pressing the number corresponding to the event displayed in each screen will dis play its default active and restoral...

Page 94: ...ormats NOTE The third character in the SIA DCS Format x in the table below represents the zone number Zone Alarm Type Ademco Contact ID SIA DCS Format Active Active Restoral Pull Station 115 FAx FHx Waterflow 113 SAx SHx Waterflow Nonsilenceable 113 SAx SHx Combo 113 SAx SHx Combo AutoResettable Supervisory 113 SAx SHx 2 Wire Detector 111 FAx FHx Normally Open Contact 110 UAx UHx Fire 110 FAx FHx ...

Page 95: ... 000 Primary Low Battery Fault 302 000 Primary No Battery Fault 311 000 Primary Telco Primary Line Fault 351 001 Primary Telco Secondary Line Fault 352 002 Primary NAC 1 Fault 321 001 Primary NAC 2 Fault 322 002 Primary NAC 3 Fault 326 003 Primary NAC 4 Fault 327 004 Primary NAC 1 Disable 521 001 Primary NAC 2 Disable 522 002 Primary NAC 3 Disable 526 003 Primary NAC 4 Disable 527 004 Primary Char...

Page 96: ...arth Fault 310 Secondary Low Battery Fault 302 Secondary No Battery Fault 311 Secondary Telco Primary Line Fault 351 Secondary Telco Secondary Line Fault 352 Secondary NAC 1 Fault 321 Secondary NAC 2 Fault 322 Secondary NAC 3 Fault 326 Secondary NAC 4 Fault 327 Secondary NAC 1 Disable 521 Secondary NAC 2 Disable 522 Secondary NAC 3 Disable 526 Secondary NAC 4 Disable 527 Secondary Charger Fault 30...

Page 97: ...e 7 Alarm FA7 FH7 Primary Zone 8 Alarm FA8 FH8 Primary Zone 9 Alarm FA9 FH9 Primary Zone 10 Alarm FA10 FH10 Primary Zone 1 Disabled FB1 FU1 Primary Zone 2 Disabled FB2 FU2 Primary Zone 3 Disabled FB3 FU3 Primary Zone 4 Disabled FB4 FU4 Primary Zone 5 Disabled FB5 FU5 Primary Zone 6 Disabled FB6 FU6 Primary Zone 7 Disabled FB7 FU7 Primary Zone 8 Disabled FB8 FU8 Primary Zone 9 Disabled FB9 FU9 Prim...

Page 98: ...ET101 ER101 Primary NAC 2 Disable ET102 ER102 Primary NAC 3 Disable ET103 ER103 Primary NAC 4 Disable ET104 ER104 Primary Charger Fault YP YQ Primary Comm Trouble Primary YC1 YK1 Primary Comm Trouble Secondary YC2 YK2 Primary Printer Fault VT VR Primary ANN Bus Fault ET61 ER61 Primary Option Card Fault ET ER Primary CS CALC Fault YF 000 Future 000 000 Primary System Off Normal LB LX Primary System...

Page 99: ...ndary Zone 8 Alarm FA8 FH8 Secondary Zone 9 Alarm FA9 FH9 Secondary Zone 10 Alarm FA10 FH10 Secondary Zone 1 Disabled FB1 FU1 Secondary Zone 2 Disabled FB2 FU2 Secondary Zone 3 Disabled FB3 FU3 Secondary Zone 4 Disabled FB4 FU4 Secondary Zone 5 Disabled FB5 FU5 Secondary Zone 6 Disabled FB6 FU6 Secondary Zone 7 Disabled FB7 FU7 Secondary Zone 8 Disabled FB8 FU8 Secondary Zone 9 Disabled FB9 FU9 Se...

Page 100: ...ry Fault YT0 YR0 Secondary No Battery Fault YT0 YR0 Secondary Telco Primary Line Fault LT1 LR1 Secondary Telco Secondary Line Fault LT2 LR2 Secondary NAC 1 Fault ET32 ER32 Secondary NAC 2 Fault ET33 ER33 Secondary NAC 3 Fault ET34 ER34 Secondary NAC 4 Fault ET35 ER35 Secondary NAC 1 Disable ET101 ER101 Secondary NAC 2 Disable ET102 ER102 Secondary NAC 3 Disable ET103 ER103 Secondary NAC 4 Disable ...

Page 101: ...gnates the number of rings allowed on the phone line prior to answering an incoming call from a service terminal The factory default is 0 which means the control panel will not answer an incoming call This entry may be programmed for 1 to 25 rings To change the Ring Count press 1 while viewing the Service Terminal Screen 2 The following screen will be displayed A flashing cursor will appear in the...

Page 102: ...ween Supervise Phone Line 2 Yes and No 3 5 6 History The History option allows an authorized user to view or erase events which have occurred in the control panel Pressing 3 while viewing Programming Screen 2 will display the History options as shown in the following display View Events Pressing 1 while viewing the History Screen will allow the user to select the events to be viewed as illustrated...

Page 103: ...5 7 Walktest Walktest allows an individual to test the fire alarm system without the necessity to reset the control panel after each device activation Refer to the sections titled Walktest on page 108 and Walk test on page 120 for additional information regarding the Walktest feature Pressing 1 while view ing the Programming Screen 3 will cause the following Walktest options to be displayed To per...

Page 104: ...nd DC is removed from the FACP the Walktest log information will be lost This information is also overwritten when subsequent walktests are performed 3 5 8 Clear Program Pressing 2 while viewing Programming Screen 3 will select the Clear Program option The con trol panel will provide a warning to the user by prompting with the following display Pressing 1 will cause the control panel to carry out ...

Page 105: ... a new five digit password such as 10101 for the Master Level After the fifth digit is entered the following screen will be displayed The new five digit password must be re entered to accept the change The display will then return to the initial Password Change Screen 3 6 Maintenance Programming Level To access Maintenance Programming mode press the Enter key The LCD will display the follow ing To...

Page 106: ...etup while viewing Maintenance Screen 1 will cause the following screens to be displayed Pressing the down arrow key will display additional Zones Zones 4 5 for SFP 5UD and Zones 4 10 for SFP 10UD Select the number corresponding to the desired zone A screen will appear which will allow enabling or disabling of the selected zone as illustrated in the following example Pressing 1 repeatedly will cau...

Page 107: ... events which have occurred press 2 while viewing the Events screen To view events other than alarms press 3 The most recent event will be displayed on the screen To view all of the selected events press the up or down arrow keys to scroll through the list of events If no events have occurred the display will read NO EVENTS IN HISTORY Pressing 2 while viewing the History Screen will cause the foll...

Page 108: ... while viewing Maintenance Screen 2 The following display will appear To change the time press 1 to display the following screen A flashing cursor will appear on the left side of the display Enter the four digit number corre sponding to the time 0000 1259 When the fourth digit is entered the cursor will move one position to the right Press 1 for AM or 2 for PM to complete entering the time The dis...

Page 109: ...er the two digit month two digit day and four digit year The cursor will move one position to the right after each entry When the fourth digit of the year has been entered the display will return to the Time and Date Screen which will show the new date To change between 12 hour and 24 hour format press 3 while viewing the Time and Date screen Each press of the 3 key will toggle the display between...

Page 110: ...SFP 5UD SFP 10UD Series Manual P N 52879 C2 1 24 2012 110 Notes ...

Page 111: ...e system NACs The Alarm Silenced LED is turned off by pressing the Reset key the Drill key or subsequent activation of the NACs Note that if Silence Inhibit has been enabled NACs cannot be silenced for one minute following initiation of an alarm 4 1 3 Drill Hold 2 Sec When the Drill key is held for a minimum of two seconds time required to prevent accidental acti vations the FACP turns on all NAC ...

Page 112: ...arm Silence key is pressed while an alarm condition exists It turns off when the Drill or Reset key is pressed 4 3 Normal Operation With no alarms or troubles in the system the display message is System All Normal along with the current time and date as shown below To set the time and date refer to the appropriate section in this manual The FACP performs the following functions at regular interval...

Page 113: ...he following information First line in display The type of event in this example OPEN indicating a circuit trouble Device type identifier in this example PULL STATION indicates a manual device Other device type identifiers which can be displayed include SMOKE for Smoke Detector HEAT for Heat Detector etc Second line in display ADJ refers to the user programmed adjective descriptor from library lis...

Page 114: ...le operation with the following differences The piezo sounder produces a steady output as opposed to a pulsed output The Fire Alarm LED flashes 1 second On and 1 second Off The LCD displays Alarm along with the device name type adjective noun associated zones and time date Communicate the alarm to the Central Station Alarms latch and are not allowed to clear automatically Timers for Silence Inhibi...

Page 115: ...event in history buffer Terminate upload or download communications A typical Supervisory event would be displayed as illustrated in the following In the preceding example FROZEN SUPRV indicates zone detector is below approximately 45o F Note that like alarms supervisory signals latch except when programmed for supervisory autore settable Supervisory activations do not cause silenced alarms to res...

Page 116: ... not activated Silenced alarms are not resounded Timers are not started Store event in history bufferActivate appropriate LED on the N ANN LED annunciator required for this application Hazard conditions latch 4 9 Medical Alert Condition Operation Medical alert operation is not intended for nurse call stations applications per UL1069 not intended for signaling professional medical staff to be used ...

Page 117: ...m verification applies to smoke detectors only 4 13 Time Functions Real Time Clock The FACP includes a crystal based clock that provides time of day date and day of week Time is displayed as 12 or 24 hour time with month day year and is stored in RAM Daylight savings time change over is programmable and automatic If both AC and battery are lost the time must be reprogrammed 4 14 Coded Operation Th...

Page 118: ...board piezo sounds immediately but the NACs are pre vented from activating for 15 seconds This inhibit time is factory set and cannot be changed Pressing the Alarm Silence or Acknowledge Step key during the 15 second inhibit time will silence the piezo sounder and start a timer which prevents activation of NACs for an additional time dura tion which can be user programmed for up to three minutes A...

Page 119: ...ving Jurisdiction 4 17 5 Alarm Verification None or One Minute If alarm verification is selected a smoke detector activation will cause the FACP to reset the detec tor by removing power for 6 seconds Power is reapplied and a 17 second retard period begins which allows all detectors to stabilize If no other detectors alarm there will be no alarm indication at the FACP during the 23 second Reset Ret...

Page 120: ...en Condition IDCs and all main circuit board NACs are monitored for fault conditions during Walktest mode When an open condition occurs on an IDC the FACP will activate all enabled NACs during an audible Walktest and remain activated until the open condition is cleared While in Walktest the trouble relay is activated and the system Trouble LED flashes as in all of the Program and status change ope...

Page 121: ...isplay will change to a screen similar to the following Pressing the down arrow key while viewing the screen shown above will allow the operator to view additional programming information about the selected device such as Enable Disable Status Device Type Alarm Verification On Off for detectors READ STATUS 1 INPUT ZONES 2 NACS 3 RELAYS READ STATUS 1 SYSTEM SETTINGS 2 TIMERS 3 DAYLIGHT SAVINGS Read...

Page 122: ...AC 2 3 to view the programmed options for NAC 3 or 4 to view the programmed options for NAC 4 The resulting screens will display the following information Enable Disable Status Coding Selection Temporal Steady etc Silenceable Nonsilenceable Auto Silence Enable Disable and time delay in minutes Silence Inhibit Enabled Disabled 4 19 3 Relays Pressing 3 while viewing Read Status Screen 1 will display...

Page 123: ...mers Pressing 2 while Read Status Screen 2 will display the following screen These screens allow the operator to view the various timer settings READ STATUS 1 SYSTEM SETTINGS 2 TIMERS 3 DAYLIGHT SAVINGS Read Status Screen 2 SYSTEM SETTINGS TROUBLE REMIND NO CANADIAN OPTION OFF CHRGR DISABLE NO SYSTEM SETTINGS USER BANNER XXX XXXXX XXXX XXXX READ STATUS 1 SYSTEM SETTINGS 2 TIMERS 3 DAYLIGHT SAVINGS...

Page 124: ...screens The operator can view all events which have been stored in the history file only alarms or other events such as troubles or supervisories by pressing the corresponding number key 4 19 8 Print To print program data or control panel status press 2 while viewing Read Status Screen 3 The following screen will be displayed DAYLIGHT SAVINGS ENABLED NO START MONTH MAR START WEEK WK 3 DAYLIGHT SAV...

Page 125: ...S Screen 1 will display BUS Module addresses 1 8 and the devices if any located at those addresses Pressing 2 while viewing ANN BUS Screen 1 will display the printer settings for the printer con nected to the FACP This information includes Serial or Parallel printer Printer Supervision Yes or No Off line Timer setting Baud Rate Data Bits Parity Stop Bits Pressing 1 while viewing ANN BUS Screen 2 w...

Page 126: ...val Account Code 24 Hour Test Time Phone Number Communication Format Event Codes This screen also displays the Call Limit for each unique DACT trouble call within a 24 hour period 4 19 11 Phone Line Pressing 1 while viewing Read Status Screen 4 will display the following screen The second and third lines of this screen indicate that both the Primary and Secondary phone lines have been configured f...

Page 127: ...ervised by the DACT The factory default setting is Phone Line 2 supervised Yes 4 19 12 Service Terminal Pressing 3 while viewing Read Status Screen 4 will display the following screens The Ring Count is displayed as the first item in the Service Terminal Screen SUPERVISE PHONE LINE PHONE LINE 2 YES READ STATUS 1 CENTRAL STATION 2 PHONE LINES 3 SERVICE TERMINAL Read Status Screen 4 SERVICE TERMINAL...

Page 128: ...SFP 5UD SFP 10UD Series Manual P N 52879 C2 1 24 2012 128 Notes ...

Page 129: ...el needs to make a call to a Central Station line seizure will disconnect any local premises phones sharing the same telephone line All transmissions to the Central Stations will be sent over the primary phone line In the event of noisy phone lines transmissions will be sent over the backup secondary phone line Two phone numbers must be programmed the primary Central Station phone number and the s...

Page 130: ...tions Waterflow Smoke detector Other alarm types 2 Supervisory Zone 3 System Troubles Zone disabled Fire drill AC fail after delay Zonal faults Earth fault Low battery Telephone line fault Notification Appliance Circuits fault Communication trouble Annunciator trouble System off normal 4 Restoral Reports Zone alarm Supervisory Zone s enabled Fire drill AC Zone fault Earth Battery Telephone line No...

Page 131: ... responsibility to ensure that the Digital Alarm Communica tor Transmitter is compatible with the Central Station Receiver utilized by the monitoring service prior to installation The Compatibility Table provides a list of compatible receivers and associated software versions for the receivers Changes in the hardware and or software by the receiver man ufacturers may affect the receiver compatibil...

Page 132: ...e fire panel s ring count from zero the default to answer after at least one ring Important Modification of FACP programming requires that the panel be enabled for download refer to Remote Download on page 132 Remote interrogation of panel programming history logs detector status etc is possible without enabling the remote download option CAUTION After successfully downloading a program make certa...

Page 133: ...emote programming downloads from the programming utility at all times without the need to access the Remote Download screen Pressing 2 for Accept Download will cause the following screen to be displayed While this screen is displayed remote programming downloads are allowed regardless of the Pro prietary setting Exiting this screen will disable any further downloads to the FACP Also follow ing 30 ...

Page 134: ...by a Service Terminal to prevent unauthorized access The secret code is created at the Service Terminal by the master user and cannot be viewed or changed by anyone other than a master user Viewing of the secret code is prohibited at the control panel Prior to allowing an upload or download of data the control panel will verify the secret code transmitted by the Service Terminal Time out at Contro...

Page 135: ...ion to a separate dedicated AC branch circuit which must be labeled FIRE ALARM This branch circuit must connect to the line side of the main power feed of the protected premises No other non fire alarm equipment may be powered from the fire alarm branch circuit The branch circuit wire must run continuously without any disconnect devices from the power source to the control panel Overcurrent protec...

Page 136: ...n amperes A Section 7 2 shows how to convert milliamperes and microamperes to full amperes 7 3 2 How to Use Table 7 3 on page 137 to Calculate System Current Draw Use Table 7 3 on page 137 to calculate current draws as follows 1 Enter the quantity of devices in all three columns 2 Enter the current draw where required Refer to the Device Compatibility Document for compatible devices and their curr...

Page 137: ... SEC card 1 max X 0 003 1 max X 0 003 1 max X 0 003 N ANN 80 C X 0 037 X 0 040 X 0 015 N ANN I O X 0 035 X 0 200 X 0 035 N ANN RLY X 0 015 X 0 075 X 0 015 N ANN R LED3 X 0 028 X 0 068 X 0 028 N ANN S PG X 0 045 X 0 045 X 0 045 2 wire Detector Heads X 4 5 X 0 040 X 4 4 wire Detector Heads X 4 5 X 0 040 X 4 Power Supervision Relays6 X 0 025 X 0 025 X 0 025 NAC 1 X NAC 2 X NAC 3 NAC 4 Current Draw fr...

Page 138: ...7 4 1 NFPA Battery Requirements NFPA 72 Local Central and Proprietary Fire Alarm Systems require 24 hours of standby power followed by 5 minutes in alarm 7 4 2 Selecting and Locating Batteries Select batteries that meet or exceed the total ampere hours calculated in Table 7 4 The control panel can charge batteries in the 7 AH to 26 AH range The control panel cabinet is capable of housing batteries...

Page 139: ...139 SFP 5UD SFP 10UD Series Manual P N 52879 C2 1 24 2012 Notes ...

Page 140: ... zone 10 A 2 Ademco Contact ID Typical Printout A typical printout from a Central Station receiver such as the Ademco 685 of alarm and trouble reports in the Ademco Contact ID Reporting Structure follows Notes 1 11 is an example of a Receiver Line Card showing which receiver and line card the message was transmitted to 2 Q which is the Event Qualifier for the reporting structure is printed out in ...

Page 141: ...Fail to report in EMERG Fail to Check in Fire Alarm 110 110 Fire Alarm FIRE Fire Alarm 111 Smoke FIRE Smoke Detector 112 Combustion FIRE Combustion 113 Waterflow FIRE Waterflow 114 Heat FIRE Heat Sensor 115 Pull station FIRE Pull Station 116 Duct FIRE Duct Sensor 117 Flame FIRE Flame Sensor 118 Near Alarm FIRE Near Alarm Panic Alarms 120 120 Panic Alarm PANIC Panic 121 Duress PANIC Duress 122 Sile...

Page 142: ...203 Gate valve sensor SUPER Gate Valve 204 Low water level SUPER Low Water Level 205 Pump activated SUPER Pump Activation 206 Pump failure SUPER Pump Failure System Troubles 300 and 310 300 System trouble TROUBLE System Trouble 301 AC loss TROUBLE AC Power 302 Low system battery TROUBLE System Low Battery 303 RAM checksum bad TROUBLE BAD RAM Checksum restore not applicable 304 ROM checksum bad TRO...

Page 143: ...Protection Loop Short 373 Fire trouble TROUBLE Fire Loop Sensor Troubles 380 380 Sensor trouble TROUBLE Sensor Trouble 381 Loss of supervision RF TROUBLE RF Sensor Supervision 382 Loss of supervision RPM TROUBLE RPM Sensor Supervision 383 Sensor tamper TROUBLE Sensor Tamper 384 RF transmitter low battery TROUBLE RF Sensor Batt Open Close 400 400 Open Close OPENING CLOSING 401 Open Close by user OP...

Page 144: ...iren 4 System Peripheral Disables 530 and 540 Communication Disables 550 and 560 551 Dialer disabled DISABLE Dialer Disable 552 Radio transmitter disabled DISABLE Radio Disable Bypasses 570 570 Zone bypass BYPASS Zone Bypass 571 Fire bypass BYPASS Fire Bypass 572 24 Hour zone bypass BYPASS 24 Hour Bypass 573 Burglar bypass BYPASS Burg Bypass 574 Group bypass BYPASS Group Bypass Test Misc 600 601 M...

Page 145: ...FOR NFPA 72 Central Station Service Protected Premises Unit or Remote Station Service Onboard Digital Alarm Communicator Transmitter for connection to a compatible listed Central Station DACR or Protected Premises Receiving Unit This unit must be installed as outlined in Digital Alarm Communicator Transmitter on page 21 OR 411UD may be installed as illustrated in Figure B 1 SFP 5UD SFP 10UD FACP C...

Page 146: ...d for Central Station Remote Station Reporting Services Figure B 1 SFP 5UD SFP 10UD FACP Connection to 411UD Channel1 Channel 2 Channel 3 Channel 4 2 2K ELR Relay Output DACT Trouble from 411UD FACP Supervisory Relay FACP Alarm Relay FACP Trouble Relay J4 Not Installed 411UD 1 2 3 4 5 6 7 8 24 VDC nonresettable power 24 VDC nonresettable power 2 2K ELRs P N 27070 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 FA...

Page 147: ...rouble or supervisory In Figure B 1 on page 146 Channel 1 Zone 1 is wired to the control panel s alarm relay Channel 2 Zone 2 is wired to the control panel s trouble relay and Channel 3 Zone 3 is wired to the control panel s supervisory relay 6 Nonresettable 24 VDC power is supplied to the 411UD via TB9 terminals configured for nonresettable power on the FACP Jumper J4 on the 411UD must be removed...

Page 148: ...llowed for wiring from control panel to Municipal Box 2 Cut JP30 on the SFP 5UD SFP 10UD main circuit board to supervise placement of SK 4XTM module and circuit 3 Cut JP24 on the SFP 5UD SFP 10UD main circuit board to enable FACP Supervisory relay 4 Refer to 4XTM Transmitter Module Installation on page 39 for detailed information FIRE Gamewell Model M34 56 Local Energy Municipal Box Polarities sho...

Page 149: ...ter Module Installation on page 39 for detailed information RS82 Remote Station Receiver UL listed Refer to Instruction Manual for Remote Station Receiver Model RS82 Polarity Shown is Normal Standby 4XTM Transmitter Module Cutting TBL Jumper allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists Power limited Figure B 3 Remote Station Connection Us...

Page 150: ...h will automatically activate on any Trouble condition Form C Alarm contact programmed to activate on General Alarm FACP Main Board Fire Alarm Control Panel Notes 1 Connection between the SFP 5UD SFP 10UD and the transmitter are supervised by the transmitter 2 This SFP 5UD SFP 10UD Transmitter arrangement can be employed for NFPA 72 Proprietary Protective Signaling System 3 Potter Electric Model E...

Page 151: ...ing End of Line Resistors ELRs with a value deter mined by the Transmitter manufacturer Power is also provided by the Central Station Remote Station Transmitter manufacturer Refer to the Central Station Remote Station Transmitter manu facturer s manual for details Figure B 5 FACP Dry Contacts Connection to Central Station Remote Station Transmitter Typical Central Station Remote Station Transmitte...

Page 152: ...F KELTRON MODULES ARE NOT SHOWN IN ACTUAL ORDER FOLLOW KELTRON MANUAL AND MODULE MARKINGS FOR EXACT TERMINAL LOCATIONS TO PREVENT SEVERE MODULE DAMAGE Fire Alarm Control Panel terminal blocks are not shown in their actual positions in order to clarify wiring connections Keltron 95M3158 TTM RPS 1 Terminals 7 and 8 Remote station alarm trouble inputs 2 Terminals 9 and 10 Sprinkler supervisory input ...

Page 153: ...r limited Communication for ANN BUS annunciator and relay modules Twisted pair a maximum loop resistance of 120 ohms 6 000 1 800 m 12 18 AWG 3 25 0 75 mm2 ANN BUS Power Power for ANN BUS annunciators Refer to Table 2 1 Wiring Distances on page 42 for information on device wiring 24 VDC Regulated resettable nonresettable Power for accessories and 4 wire devices Untwisted unshielded wire Distance li...

Page 154: ... 249 156 98 62 124 78 49 31 Table D 2 NAC Wiring Requirements for FACP with FLPS 3 Power Supply NOTE Calculations are based on Direct Current Resistance data for uncoated copper wire per National Electrical Code 2005 Edition Table 8 Conductor Properties NAC Load Amps Max allowable total loop resistance ohms CLASS B Max allowable wire pair length feet CLASS A Max allowable wire pair length feet AWG...

Page 155: ...harger Disable No ANN BUS Relay 6 type Zone 6 Factory Banner Factory Banner ANN BUS Relay 7 type Zone 7 PAS Timer 120 ANN BUS Relay 8 type Zone 8 Pre Signal Timer 120 ANN BUS Relay 9 type Zone 9 AC Loss Timer 2 ANN BUS Relay 10 type Zone 10 Waterflow Delay Timer 0 Phone Line 2 Supervision Yes Time Format 12 Hour Primary Phone Type Touchtone Daylight Savings Enabled Yes Secondary Phone Type Touchto...

Page 156: ...ction of this manual If remote indicators are desired they must be connected to the secondary ANN BUS circuit This requires the use of the ANN SEC option card The installer must write in the Date of Final Assembly on the Master Marking and Warranty Label located on the FACP backbox door To comply with CAN ULC S559 04 the N ANN RLY option must be utilized along with the configuration shown in Figur...

Page 157: ... N ANN RLY must be programmed for supervisory activation with latching non latching set in accordance with the local AHJ 4 The N ANN RLY must be mounted inside the FACP cabinet 5 Refer to the N ANN RLY Document 53318 for installation instructions Figure F 2 Alternate Transmission for Alarm Trouble and Supervisory Signals FACP N ANN RLY ALARM TROUBLE SUPERVISORY C NC NO C NC NO C NC NO C NC NO C NC...

Page 158: ...ry power 33 Auxiliary Trouble Input 17 B backbox dimensions 21 mounting 26 Backup Reporting 90 Banner 75 setting 78 battery 21 29 precautions 29 rating 15 battery box 22 mounting 27 28 battery calculations 138 buttons see also control buttons 14 C cabinet mounting 26 CAC 5X 30 installation 37 call limit 58 100 Canadian Applications 24 Canadian Option 75 81 Central Station 90 134 account code 92 co...

Page 159: ...ee also smoke detector monitoring 13 G guidelines 41 H Hazard Condition 116 History 102 erase 103 Maintenance Level 107 view events 102 I I3 detectors 30 IDC 14 16 30 alarm current 16 compatibility 30 End of_Line resistor 31 End of Line resistor 16 30 maximum loop resistance 16 30 short circuit current 16 standby current 16 wiring 30 indicators 20 see also LED 15 Initiating Device Circuit 14 16 30...

Page 160: ...aling System 149 NFPA Standard 145 NFS LBB see also battery box 22 nonpower limited wiring 35 nonresettable power 13 16 33 current 33 maximum current 16 Normal 112 normal display 58 Notification Appliance Circuit 13 16 32 70 Class A 38 Noun list 68 multiple entries 69 O Operating Instructions 111 Operation alarm 114 disable enable 117 hazard condition 116 medical alert 116 normal 112 process monit...

Page 161: ...Silence Inhibit 74 118 Silenceable NAC 73 silenceable circuits synchronized signals 73 sounder 15 20 strobes 15 72 Style B 16 30 see also Class B 14 Style D 21 30 38 Style Y 16 see also Class B 14 Style Z 21 38 subscreen 60 supervision Transmitter option module placement 39 supervisory 13 115 piezo pulse rate 20 supervisory relay 33 contact rating 16 synchronization 72 synchronized 72 synchronized...

Page 162: ... 108 operation 120 silent 103 Waterflow Delay timer 76 77 Waterflow Retard Timer 119 Wire Requirements 153 wiring CAC 5X 38 Class A Converter Module 38 Class A IDC 38 Class A NAC 38 combination waterflow supervisory 31 IDC 30 NAC 32 nonpower limited 35 power limited 35 UL requirements 35 Z Zone type 63 verification 65 Zone Setup Maintenance Level 106 ...

Page 163: ...LIED WITH RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF OR AS A RESULT OF PERSONAL COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS This document constitutes the only...

Page 164: ...World Headquarters 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www notifier com ...

Reviews: