NOTI•FIRE•NET
™,
IntelliQuad
™, and
ONYXWorks
™ are trademarks; and
Acclimate® Plus™, FirstCommand
®,
FlashScan
®,
NOTIFIER
®,
ONYX
®,
VeriFire®
, and
VIEW
® are registered trademarks of Honeywell International
Inc.
Microsoft
® and
Windows
® are registered trademarks of Microsoft
Corporation.
IBM
® is a registered trademark of IBM Corporation.
©2013 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
Page 6 of 6 — Canadian DN-60085:J • 12/20/2013
This document is not intended to be used for
installation purposes. We try to keep our
product information up-to-date and accurate.
We cannot cover all specific applications or
anticipate all requirements. All specifications are
subject to change without notice.
For more information, contact Notifier.
(888) 289-1114
10 Whitmore Road
Woodbridge, Ontario LZL 7Z4
www.notifier.com
intelligent DCL equipment), and the Device Compatibility Docu-
ment.
System Specifications
S
YSTEM
C
APACITY
•
Intelligent Digital Communications Loop (DCL) ................. 1
•
Intelligent detectors ....................................................... 159
•
Addressable monitor/control modules ............................ 159
•
Programmable internal hardware and output circuits ........ 4
•
Programmable software zones ......................................... 99
•
Special programming zones ............................................. 14
•
LCD annunciators per FACP ............................................ 32
•
ACS annunciators per FACP ........ 32 addresses x 64 points
S
PECIFICATIONS
•
Primary input power
:
120 VAC, 50/60 Hz, 5.0 A.
•
Current draw (standby/alarm):
–
NFS-320C board: 0.250 A. Add 0.035 A for each NAC in
use.
–
KDM-R2 (Backlight on): 0.100 A.
•
Total output 24 V power: 6.0 A in alarm.
NOTE:
The power supply has a total of 6.0 A of available power.
This is shared by all internal circuits.
•
Standard notification circuits (4): 1.5 A each.
•
Resettable regulated 24V power: 1.25 A.
•
Two non-resettable regulated 24V power outputs. One at
1.25 A and the other at 0.50 A.
•
Non-resettable 5V power: 0.15 A.
•
Battery charger range: 18 AH – 200 AH. Use separate cab-
inet for batteries over 26 AH.
•
Float rate: 27.6 V.
C
ABINET
S
PECIFICATIONS
•
NFS-320C cabinet dimensions:
–
Backbox: 18.12 in. (46.025 cm) width; 18.12 in. (46.025
cm) height; 5.81 in. (14.76 cm) depth.
–
Door: 18.187 in. (46.195 cm) width; 18.40 in. (46.736 cm)
height; 0.75 in. (1.905 cm) depth.
When using trim ring TR-320, mount backbox with at least 1
inch (2.54 cm) between wall surface and front of backbox, to
allow door to open fully past the trim ring. The TR-320 molding
width is 0.905 in. (2.299 cm).
S
HIPPING
W
EIGHT
–
NFS-320C: 37 lb (16.78 kg)
without batteries.
T
EMPERATURE
AND
H
UMIDITY
R
ANGES
This system meets NFPA requirements for operation at 0 –
49°C and at a relative humidity 93% ± 2% RH (noncondens-
ing) at 32°C ± 2°C. However, the useful life of the system's
standby batteries and the electronic components may be
adversely affected by extreme temperature ranges and humid-
ity. Therefore, it is recommended that this system and its
peripherals be installed in an environment with a normal room
temperature of 15 – 27°C.
A
GENCY
L
ISTINGS
AND
A
PPROVALS
The listings and approvals below apply to the basic NFS-320C
control panel. In some cases, certain modules may not be
listed by certain approval agencies, or listing may be in pro-
cess. Consult factory for latest listing status.
•
UL/ULC Listed:
S635 (UOJC).
•
FM Approved.
•
CSFM:
7165-0028:0243.
•
FDNY:
COA#6085, #6121.
Marine Applications:
Marine approved systems must be con-
figured using components itemized in this document. (See
Main System Components, in “Product Line Information.) Spe-
cific connections and requirements for those components are
described in the installation document, PN 54756. When these
requirements are followed, systems are approved by the fol-
lowing agencies:
•
US Coast Guard:
161.002/50/0, 161.002/55/0 (Standard
46 CFR and 161.002).
•
Lloyd's Register:
11/600013 (ENV 3 category).
•
American Bureau of Shipping.
NOTE:
For information on marine applications, see DN-60688.
S
TANDARDS
The NFS-320C complies with the following ULC Standards
and NFPA 72, International Building Code (IBC), and Califor-
nia Building Code (CBC) Fire Alarm Systems requirements:
•
ULC-S527-99.
•
LOCAL
(Automatic, Manual, Waterflow and Sprinkler
Supervisory).
•
AUXILIARY
(Automatic, Manual and Waterflow) (requires
TM-4).
•
REMOTE STATION
(Automatic, Manual, Waterflow and
Sprinkler Supervisory) (requires TM-4).
•
PROPRIETARY
(Automatic, Manual, Waterflow and Sprin-
kler Supervisory).
Not applicable for FM.
•
CENTRAL STATION
(Automatic, Manual, Waterflow and
Sprinkler Supervisory) (requires DACT).
•
EMERGENCY VOICE/ALARM
.
•
IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000
(Seis-
mic).
•
CBC 2007
(Seismic).